17
Note: This document is based on the recommendatio ns of BS5839 Part 1: 2002. I t is intended only as a guide to the ap plication of fire detection systems.
Reference must be made to relevant national and local stan dards.
Application Guide
2.6 MAINTENANCE OF FIRE DE TECTORS
Caution: Prior to carrying out any mai ntenance or testing
on a fire alarm system, the relevant authorit ies and staff
should be notified.
Over time, the sensitivity of a smoke detec tor can change
owing to a build-up of dirt in the detector cha mber. In most
modern detectors this effec t is slowed by the inclusion of drift
compensation functions, however the build u p can still lead to
a risk of false alarms or change in the detect or sensitivity.
The frequency of maintenance requireme nts on a detector will
depend on site conditions, obviously the di rtier the site the
more frequent maintenance will be require d. The optimum
frequency for a given site should be determin ed over a period
of time after the commissioning of the fire sys tem.
All System Sensor detectors ( smoke, heat, or multi-criteria )
are designed such that they can be easily disman tled for
maintenance. Instructions are give n for maintenance in the
instruction manual supplied with each de tector. Normally it
is sufficient to use compressed air or a vac uum cleaner to
remove dust from the detector chamber.
Once maintenance on a fire detection sys tem has been
completed, it should be re-tested.
2.7 ROUTINE FUNCTIONAL TE STING OF FIRE DETECTORS
BS5839 Part 1: 2002 give s a range of recommendations
regarding routine testing of a fire detec tion system.
A weekly test should be carried out on a fire de tection system
by activating a manual call point to ensure tha t all fire alarm
signals operate correctly, and that the ap propriate alarm
signals are clearly received. This test sho uld be carried out at
approximately the same time each week, using a dif ferent call
point in rotation.
In order to comply with BS5839 Pa rt 1: 2002, periodic
inspections, servicing and funct ional tests of the fire alarm
system should be carried out at inter vals determined by
an assessment of the site and type of sy stem installed, not
normally greater than six months.
It is recommended to perform regular f unctional tests on all
fire detectors annually. These annual tes ts may be carried
out over the course of two or more servic e visits during the
twelve-month period.
System Sensor detectors include va rious means of testing the
system without using smoke, dependent on the de tector range
being tested, including magnet switches and la ser test tools.
Codes and standards (in the UK B S5839 Part 1:20 02, Section
6) now require functional tests t o introduce smoke through
the smoke detector vents and into the sensi ng chamber. It also
calls for heat detectors to be tested b y means of a suitable
heat source, and not by a live flame. CO fire detect ors now
also need to be functionally tested by a met hod that confirms
that carbon monoxide can enter the chambe r.
Many installers use a set of equipment tha t consists of a
complete range of test tools that locat e on the end of the pole
such as those available from No Climb Produc ts Ltd. (www.
noclimb.com) in order to aid compliance wit h codes. Tools
exist for testing smoke, heat, and CO fire de tectors, whilst
also enabling them to be accessed and removed at heig hts up
to 9 meters from the ground.
Using functional test equipment, alo ng with those
maintenance tools available from Syste m Sensor, should
ensure that the system remains at its opt imum operation for
many years.