INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range
3825 Ohio Avenue, St. Charles, Illinois 60174
The Innovair DH100ACDCLP model is a photoelectric | (alarm initiation), HVAC control, and other auxiliary func- | |||||
detector approved for an extended air speed range of 100 to | tions. Auxiliary relays are also provided for fan shut down | |||||
4000 feet per minute (0.5 m/s to 20.3 m/s) and an opera- | or signaling of up to 9 other detectors in the loop for mul- | |||||
tional temperature range of 32°F to 131°F (0°C to 55°C). |
| tiple fan shut down. These detectors are not designed for | ||||
Before Installing |
|
| ||||
|
|
|
|
| ||
Please thoroughly read the System Sensor Guide for Proper | For testing, the alarm can be enabled by a magnet activated | |||||
Use of Smoke Detectors in Duct Applications | test switch or by the optional remote test station. The duct | |||||
which provides detailed information on detector spacing, | smoke detector latches into alarm state when an alarm | |||||
placement, zoning, wiring, and special applications. Copies | occurs. A green LED flashes to indicate power, a red LED | |||||
of this manual are available online at www.systemsensor.com | signals local alarm indication, and optional accessories | |||||
or via System Sensor’s toll free | offer a variety of annunciation capabilities. | |||||
on Demand at | The DH100ACDCLP can be reset by a momentary power | |||||
should also be referenced for detailed information. |
|
| ||||
|
| interruption, the reset button on the front cover, the con- | ||||
NOTICE: This manual shall be left with the owner/user of | ||||||
trol panel, or remote reset accessory. The DH100ACDCLP | ||||||
this equipment. |
|
| incorporates a cover tamper feature that provides a | |||
IMPORTANT: This detector must be tested and maintained | trouble signal after 7 minutes if the cover is removed | |||||
or improperly installed. Proper installation of the cover | ||||||
regularly following NFPA 72 requirements. The | detector | |||||
removes the trouble condition. | ||||||
should be cleaned at least once a year. |
|
| ||||
|
|
|
|
| ||
Table of Contents | Page | [2] Limitations Of Duct Smoke Detectors | ||||
[1] General Description | 1 |
|
|
| ||
[2] Limitations of Duct Smoke Detectors |
| 1 |
|
| ||
| WARNING |
| ||||
......[3] Exploded View of Duct Smoke Detector Components | 2 | The National Fire Protection Association has established that | ||||
[4] Contents of the Duct Smoke Detector Kit | 2 | |||||
DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE | ||||||
[5] Installation Sequence | 2 | |||||
FOR OPEN AREA DETECTOR PROTECTION as a means of | ||||||
[6] Duct Smoke Detector Maintenance and Test Procedures | 5 | |||||
providing life safety. Nor are they a substitute for early warn- | ||||||
[7] Detector Cleaning Procedures | 7 | |||||
ing in a building’s regular fire detection system. | ||||||
[8] Board Replacement | 8 | |||||
System Sensor supports this position and strongly recom- | ||||||
[9] Specifications | 8 | |||||
mends that the user read NFPA Standards 90A, 72, and 101. | ||||||
Warranty | 8 | |||||
The DH100ACDCLP Air Duct Smoke Detectors are listed per | ||||||
|
|
| ||||
[1] General Description |
|
| UL 268A. | |||
An HVAC system supplies conditioned air to virtually every |
|
|
| |||
|
|
| ||||
| WARNING |
| ||||
area of a building. Smoke introduced into this | air duct |
|
| |||
|
|
| ||||
This device will not operate without electrical power. | ||||||
system will be distributed throughout the entire building. | ||||||
Fire situations may cause an interruption of power. The | ||||||
Smoke detectors designed for use in air duct systems are | ||||||
system safeguards should be discussed with your local | ||||||
used to sense the presence of smoke in the duct. |
|
| ||||
|
| fire protection specialist. | ||||
Model DH100ACDCLP Air Duct Smoke Detector utilizes | ||||||
|
|
| ||||
photoelectric technology for the detection of smoke. This |
|
| ||||
| WARNING |
| ||||
detection method, when combined with an efficient hous- | This device will not sense smoke unless the ventilation | |||||
ing design, samples air passing through the duct and allows | ||||||
system is operating and the cover is installed. | ||||||
detection of a developing hazardous condition. When suf- | ||||||
|
|
| ||||
ficient smoke is sensed, an alarm signal is initiated and |
|
| ||||
| WARNING |
| ||||
appropriate action can be taken to shut off fans, blowers, | For this detector to function properly, it MUST be installed | |||||
change over air handling systems, etc. These actions can | ||||||
according to the instructions in this manual. Furthermore, | ||||||
facilitate the management of toxic smoke and fire gases | ||||||
the detector MUST be operated within ALL electrical and | ||||||
throughout the areas served by the duct system. |
|
| ||||
|
| environmental specifications listed in this manual. Failure | ||||
|
|
| ||||
The DH100ACDCLP detector is designed to operate on | to comply with these requirements may prevent the detec- | |||||
24 VDC/VAC, 120 VAC, or 240 VAC. Alarm and supervi- | tor from activating when smoke is present in the air duct. |
sory relay contacts are available for control panel interface
1 |