[4]Contents Of The Duct Smoke Detector Kit

[3] Figure 1: Exploded View of Duct Smoke Detector Components

FOAM

GASKETS

CONDUIT HOLES

DETECTOR

SAMPLING TUBEHOUSING

FILTERS

METAL

 

SAMPLING TUBE

TERMINAL STRIP

 

POWER BOARD

Manual background COVER MOUNTING

SCREWS

DETECTOR BOARD

DETECTOR

 

COVER

H0165-00

 

[4]Contents Of The Duct Smoke Detector Kit

1. Complete housing base and cover assembly

2. Two #10 x 11/4sheet metal screws for mounting

3. Two sampling tube filters

4. One test magnet

5. Drilling template

6. Two foam gaskets

7. Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension

8. One sampling tube end cap

9. One plastic sampling tube

10. One #8 self-tapping screw for the plastic sampling tube NOTE: For ducts over 112 feet, longer sampling tubes must be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the inlet tube required for different

duct widths.

[5]Installation Sequence

[5.1] Verify Duct Air Flow Direction And Velocity Model DH100ACDCLP detectors are designed to be used in air handling systems having air velocities of 100 to 4000 feet per minute. Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters. If necessary, use a velocity meter (anemom- eter) to check the air velocity in the duct.

[5.2] Drill The Mounting Holes

Remove the paper backing from the mounting template supplied. Affix the template to the duct at the desired mounting location. Make sure the template lies flat and smooth on the duct. Center punch holes A and B. Drill the holes as indicated on the template.

[5.2.1] Sampling Tube Installation for Ducts Less Than 112 Feet Wide (see Figure 2)

1.Remove the front cover.

2.Slide the plastic sampling tube into the housing bushing.

3.Align the holes in the bushing with the holes in the sampling tube. Make sure there are 6 exposed holes on the plastic sampling tube. Secure with the #8 self-tapping screw into the bottom of the permanent tube (shown in Fig. 2).

NOTE: The sampling tube end cap is critical to the proper operation of the duct smoke detector. The end cap is needed to create the proper air flow to the sensor of the duct smoke detector.

NOTE: For ducts greater than 112 feet in width, refer to sections [5.4.1] and [5.4.2].

Figure 2. Plastic sampling tube connected to duct smoke detector:

H0110-00

[5.3] Secure The Detector Housing To The Duct

Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the two 11/4long sheet metal screws to screw the detector housing to the duct.

CAUTION: Do not overtighten the screws.

Figure 3. Installation of foam gaskets over sampling tube bushings:

SCREW HOLES FOR

ATTACHING HOUSING

TO DUCT WORK.

H0107-00

D200-14-00

2

I56-0084-08R

Page 2
Image 2
System Sensor DH100ACDCLP specifications 4Contents Of The Duct Smoke Detector Kit