Figure 8. System wiring diagram for
CAUTION
Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.
POWER INPUTS ACCEPT 24 VDC, 24 VAC
AUX. CONTACT RATINGS 10A @ 30 VDC RESISTIVE 100mA MINIMUM @ 5 VDC 1/4 HP @ 240 VAC 1/8 HP @ 120 VAC NOT INTENDED FOR CONNECTION TO CONTROL PANELS.
TROUBLE CONTACT RATING
2.0A @ 30 VDC resistive
2.0A @ 125 VAC resistive
+
ALARM
INITIATION
LOOP
UL LISTED
CONTROL PANEL
| AVAILABLE POWER INPUTS |
| ||
9 | 10 | A | B | C |
| 24V |
| 120 |
|
|
|
| VAC |
|
| |
|
|
|
|
| |
|
|
| 220/240 |
| |
|
|
| VAC |
|
|
| ALARM AUXILIARY CONTACTS |
| |||
| FOR FAN SHUTDOWN, ETC. |
| |||
16 | 6 | 17 | 7 | 18 | 8 |
N.C. | C. | N.O. | N.O. | C. | N.C. |
ALARM AUXILIARY CONTACTS SHOWN IN | |||||
STANDBY. CONTACTS TRANSFER DURING | |||||
ALARM AS INDICATED BY THE ARROWS. | |||||
SUPERVISORY TROUBLE CONTACTS |
| ||||
| 14 |
|
| 3 |
|
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. | |||||
CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS | |||||
REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN | |||||
CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. | |||||
|
| 5 |
|
|
|
ALARM |
| CONTACTS SHOWN | |||
INITIATION |
| OPEN IN STANDBY. | |||
CONTACTS |
| CONTACTS CLOSE | |||
|
|
| IN ALARM. |
| |
|
| 4 |
|
|
|
| FIRST DETECTOR IN THE LOOP |
| |||
| DH100ACDCLP |
|
|
|
| AVAILABLE POWER INPUTS |
| ||
9 | 10 | A | B | C |
| 24V |
| 120 |
|
|
|
| VAC |
|
| |
|
|
|
|
| |
|
|
| 220/240 |
| |
|
|
| VAC |
|
|
| ALARM AUXILIARY CONTACTS |
| |||
| FOR FAN SHUTDOWN, ETC. |
| |||
16 | 6 | 17 | 7 | 18 | 8 |
N.C. | C. | N.O. | N.O. | C. | N.C. |
ALARM AUXILIARY CONTACTS SHOWN IN | |||||
STANDBY. CONTACTS TRANSFER DURING | |||||
ALARM AS INDICATED BY THE ARROWS. | |||||
SUPERVISORY TROUBLE CONTACTS |
| ||||
| 14 |
|
| 3 |
|
TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. | |||||
CONTACTS OPEN WHILE DETECTOR PCB OR POWER IS | |||||
REMOVED OR WHEN TAMPER FEATURE TIMES OUT. OPEN | |||||
CONTACTS SIGNAL TROUBLE CONDITION TO PANEL. | |||||
|
| 5 |
|
|
|
ALARM |
| CONTACTS SHOWN | |||
INITIATION |
| OPEN IN STANDBY. | |||
CONTACTS |
| CONTACTS CLOSE | |||
|
|
| IN ALARM. |
| |
|
| 4 |
|
|
|
| LAST DETECTOR IN THE LOOP |
| |||
| DH100ACDCLP |
|
|
|
CONNECT POWER SOURCE
TO APPROPRIATE TERMINALS
OF EACH DETECTOR. SEE
SPECIFICATIONS FOR
ADDITIONAL POWER SUPPLY
INFORMATION.
FOR WIRING OF AUXILIARY
DEVICES, REFER TO
MANUFACTURER'S
INSTALLATION INSTRUCTIONS
OR CONTACT MANUFACTURER.
NOTE: THE SUPERVISORY RELAY NOW PROVIDES A "FORM C" CONTACT FOR CUSTOMIZED APPLICATIONS. FOR STANDARD APPLICATIONS, ONLY THE "NO" CONTACT IS USED
EOL RESISTOR
SPECIFIED BY
PANEL MANUFACTURER
Figure 9. Wiring diagram for DH100ACDCLP to APA451:
DH100ACDCLP |
| APA451 | |
Alarm Signal | 15 | 2 | Alarm |
|
|
| (Red LED) |
Aux. Power + | 19 |
|
|
Sup. N. O. | 14 |
|
|
Sup. COM | 3 | 3 | Power |
|
|
| (Green LED) |
Aux. Power – | 20 | 1 | Common |
NOTE: Wiring diagram shown is for DH100ACDCLP
Figure 10. Wiring diagram for DH100ACDCLP to RTS451/RTS451KEY:
DH100ACDCLP |
| RTS451/RTS451KEY | |
Alarm Signal | 15 | 1 | (Red LED) Alarm |
Aux. Power + | 19 |
| * |
|
|
| For RTS451KEY |
Sup. N. O. | 14 |
| *only without a |
| control panel. | ||
Sup. COM | 3 | 6 | (Green LED) |
|
|
| Power |
Aux. Power – | 20 | 2 |
|
|
|
| |
Reset | 2 | 3 |
|
|
| 4 |
|
Test | 11 | 5 |
|
Figure 11. Multiple fan shutdown (interconnect):
Important Interconnect Notes
1 | 6 | A B C |
12 | 16 |
|
|
| DETECTOR 1 |
|
| SYSTEM |
FAN |
| CONTROL |
CONTROL |
| POWER OR |
|
| THERMOSTAT |
1 | 6 | A B C |
12 | 16 |
|
|
| DETECTOR 2 |
|
| SYSTEM |
FAN |
| CONTROL |
CONTROL |
| POWER OR |
|
| THERMOSTAT |
OUT TO
10DETECTORS MAXIMUM
1 | 6 | A B C |
|
|
|
1216
DETECTOR 10
|
| SYSTEM |
FAN |
| CONTROL |
CONTROL |
| POWER OR |
|
| THERMOSTAT |
|
|
|
•When using the interconnect feature, all interconnected units must be powered with the same, independent supply.
•Polarity must be maintained throughout the interconnect wiring. Connect termi- nal 12 on unit 1 to terminal 12 on unit 2 and so on. Similarly, connect terminal 1 on unit 1 to terminal 1 on unit 2 and so on.
•Up to 10 units may be interconnected.
6 |