System Sensor DH500ACDC specifications Flange

Models: DH500ACDC

1 12
Download 12 pages 33.58 Kb
Page 3
Image 3
FLANGE

Figure 2. Speed nut mounting location:

HOLE B

HOLE A

DUCT

WALL

SPEED

NUT Manual background

H0116-00

CAUTION: Do not overtighten the screws.

Exception: Where it is physically impossible to locate the detector accordingly, the detector can be positioned closer than six duct widths, but as far as possible from the open- ing, bend, or deflection plates.

Step 3. Mount Duct Housing

Remove the duct housing cover. Slide the foam gaskets over the tube bushings as shown in Figure 2A. Make sure the two small holes in the gaskets line up with the two duct housing mounting holes. Put one 5/16-inch O-ring over each of the two #10 sheet metal screws. Use the two sheet metal screws to secure the duct housing to the duct.

Table 1. Sampling (Inlet) Tubes

 

TUBE

OUTSIDE DUCT WIDTH

ST-1.5

1 to 2 ft.

(0.3 to 0.6 m)

ST-3

2 to 4 ft.

(0.6 to 1.2 m)

ST-5

4 to 8 ft.

(1.2 to 2.4 m)

ST-10

8 to 12 ft.

(2.4 to 3.7 m)

Figure 3. Air duct detector inlet sampling tube:

Figure 2A. Installation of foam gaskets over sam- pling tube bushings:

MOUNTING

SAMPLING

DUCT DETECTOR

TUBE BUSHING

HOUSING

SCREWS

 

 

O-RINGS

 

EXHAUST TUBE

 

 

(EXTENSION BUSHING)

 

 

FOAM

 

 

GASKETS

SCREW HOLES FOR ATTACHING

DETECTOR HOUSING TO DUCT

H0117-00

Step 4. Install The Inlet Tube

The inlet tube (shown in Figure 3) is identified by a series of air inlet holes on the tube. This tube must be purchased separately. Order the correct length, as specified in Table 1, for the width of the duct where it will be installed. The exhaust tube is molded into the base of the duct housing.

The inlet tube should be installed in the inlet sampling tube bushing located in the center of the duct detector housing. (See Figure 2A.) The air inlet holes must face into the air flow. To assure proper installation, the tube mount- ing flange is marked with arrows. Mount the inlet tube so that the arrows point into the air flow. Figure 4 shows the various combinations of duct detector and tube mounting configurations with respect to air flow.

FLANGE

AIR HOLES

INLET

 

 

 

TUBE

 

 

END

 

 

PLUG

ARROWS

AIR FLOW DIRECTION

H0108-00

MUST FACE

 

 

INTO AIR FLOW

D500-07-00

3

I56-432-11R

Page 3
Image 3
System Sensor DH500ACDC specifications Flange