Data Sheet: PoweretaTM iQP Series –Single Output Quarter Brick

Electrical Data:

iQP48050A050V-000 through -0x9: 5V, 50A, 250W Output

 

Characteristic

Min

 

Typ

 

 

Max

 

 

Unit

 

Notes & Conditions

 

Output Voltage Initial Setpoint

4.88

 

5

 

5.12

 

 

Vdc

 

Vin=Vin,nom; Io=Io,max; Tc = 25˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage Tolerance

4.85

 

5

 

5.15

 

 

Vdc

 

Over all rated input voltage, load, and

 

 

 

 

 

 

temperature conditions to end of life

 

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency

---

 

91.5

 

---

 

%

 

Vin=Vin,nom; Io=Io,max; Tc = 25˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

Line Regulation

---

 

1

 

10*

 

 

mV

 

Vin=Vin,min to Vin,max, Io and Tc fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

Load Regulation

---

 

1

 

10*

 

 

mV

 

Io=Io,min to Io,max, Vin and Tc fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature Regulation

---

 

5

 

50

 

 

mV

 

Tc=Tc,min to Tc,max, Vin and Io fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At loads less than Io,min the module will

 

Output Current

5

 

---

 

50

 

 

A

 

continue to regulate the output voltage, but

 

 

 

 

 

 

 

 

 

 

 

 

the output ripple may increase slightly

 

Output Current Limiting Threshold

---

 

55

 

---

 

 

A

 

Vo = 0.9*Vo,nom, Tc<Tc,max

 

Short Circuit Current

---

 

2

 

---

 

 

A

 

Vo = 0.25V, Tc = 25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

---

 

50

 

100*

 

 

mVpp

 

Vin=48V, Io Io,min, Tc=25˚C. Measured

 

 

 

 

 

 

 

across one 0.1uF, one 1.0 uF, and one

 

 

 

 

 

 

 

 

 

Output Ripple and Noise Voltage

 

 

 

 

 

 

 

 

 

 

47uF ceramic capacitors, and one 1000uF

 

 

 

 

 

 

 

 

 

 

 

electrolytic capacitor located 2 inches away

 

 

 

 

 

 

 

 

 

 

 

 

 

 

---

 

13.5

 

---

 

 

mVrms

 

– see input/output ripple measurement

 

 

 

 

 

 

 

figure; BW = 20MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage Adjustment Range

80

 

---

 

110

 

 

%Vo,nom

 

Vin 38V for trim-up operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage Sense Range

---

 

---

 

10

 

 

%Vo,nom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dynamic Response:

 

 

 

 

 

 

 

 

 

 

di/dt = 1A/uS, Vin=Vin,nom; load step from

 

 

 

 

 

 

 

 

 

 

 

50% to 75% of Io,max, Tc=25˚C with at

 

 

 

 

 

 

 

 

 

 

 

 

 

Recovery Time to 10% of Peak Deviation

---

 

400

 

---

 

 

S

 

least one 1.0 uF, one 47uF ceramic

 

 

 

 

 

 

capacitors, and one 1000uF electrolytic

 

 

 

 

 

 

 

 

 

 

 

 

 

Transient Voltage

---

 

150

 

---

 

 

mV

 

capacitor across the output terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage Overshoot during startup

0

 

0

 

---

 

 

mV

 

Vin=Vin,nom; Io=Io,max,Tc=25˚C

 

 

 

 

 

 

 

 

 

 

 

 

 

Switching Frequency

---

 

145

 

---

 

 

kHz

 

Fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Over Voltage Protection

5.8*

 

6.1

 

6.5*

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Load Capacitance

1000

 

---

 

 

25,000

 

uF

 

Cext,min required for the 100% load dump.

 

 

 

 

 

 

Minimum ESR > 2 m

 

 

 

 

 

 

 

 

 

 

 

 

 

Isolation Capacitance

---

 

1000

 

---

 

 

pF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Isolation Resistance

15

 

---

 

---

 

 

MΩ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vref

 

 

1.225

 

 

 

 

 

V

 

Required for trim calculation

 

 

 

 

 

 

 

 

 

 

 

 

 

* Engineering Estimate

Contact TDK Innoveta for applications that require additional capacitance or very low ESR

©2005-2006 TDK Innoveta Inc.

(877) 498-0099

5/15

iQP 5V/50A Datasheet 8/3/2006

 

Page 5
Image 5
TDK iQP 5V/50A manual Electrical Data, IQP48050A050V-000 through -0x9 5V, 50A, 250W Output