2103 Modem Module

Section 4 Modbus Protocol

The register definitions for the individual modules (Modbus

ASCII addresses 2-(N+1)) are in Table 4-1below:

Table 4-2 Modbus ASCII Address 2-(N+1) Register Definitions

Register Number(s)

Name

Data Type

Units

Read/Write

1-4

Model number

8-byte string

None

Read

 

 

 

 

 

5-23

Module name

38-byte string

None

Read

 

 

 

 

 

241

Identify module

16 bit integer

None

Read/Write

252

Take reading flag

16 bit integer

None

Read/Write

263

Update interval

16 bit integer

Seconds

Read/Write

274

Active flag 1

16 bit field

None

Read

28

Active flag 2

16 bit field

None

Read

 

 

 

 

 

29

Active flag 3

16 bit field

None

Read

 

 

 

 

 

30

Active flag 4

16 bit field

None

Read

 

 

 

 

 

40,41

Level

4-byte float

Meters

Read

 

 

 

 

 

42

Level status code5

16-bit integer

 

Read

43-52

Level time record

Time6

 

Read

55,56

Velocity

4-byte float

Meters/second

Read

 

 

 

 

 

57

Velocity status code

16-bit integer

 

Read

 

 

 

 

 

58-63

Velocity time record

Time

 

Read

 

 

 

 

 

70,71

Flow

4-byte float

Cubic Meters/sec

Read

 

 

 

 

 

72

Flow status code

16-bit integer

 

Read

 

 

 

 

 

73-78

Flow time record

Time

 

Read

 

 

 

 

 

85,86

Flow 1

4-byte float

Cubic Meters/sec

Read

 

 

 

 

 

87

Flow 1 status code

16-bit integer

 

Read

 

 

 

 

 

88-93

Flow 1 time record

Time

 

Read

 

 

 

 

 

100,101

Volume

4-byte float

Cubic Meters

Read

 

 

 

 

 

102

Volume status code

16-bit integer

 

Read

 

 

 

 

 

103-108

Volume time record

Time

 

Read

 

 

 

 

 

115,116

Volume 1

4-byte float

Cubic Meters

Read

 

 

 

 

 

4-7

Page 33