2.5 Testing
Verify the wiring connections.
WARNING! ONLY CONNECT THE WHITE WIRE TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE MAY RESULT.
After checking the wiring, this short test will confirm proper
1.Install front cover of the DEH 3000R; connect the top first, then the bottom.
2.Plug in the
3.Turn the DEH 3000R ON by pressing the “ON/OFF” button.
4.Verify dehumidification operation by adjusting the RH “SETPOINT” to below the “%RH” reading on the display. Use the down “RH” button. Confirm
Increase the RH “SETPOINT” on the display to well above the “%RH” reading on the display. Press the “RH” up arrow to increase the RH “SETPOINT”.
After running the dehumidifier compressor the DEH 3000R applies a 10 minute restart lockout on all functions. You will have to wait for the restart lockout to expire.
5.Verify
a.Check the “VENT” mode on the display, it will either be “CLOSED” or “OPEN”. If it is “CLOSED” go to the next step. If it is “OPEN”, press and hold the “VENT” key until “OPEN” flashes on the display, release the key and then press it one more time. “OPEN” will change to “CLOSED”. Don’t touch the keys for several seconds until it stops flashing.
b.Press and hold the “FAN” button until “AUTO” begins flashing on the display, release it, and then press it again to switch the fan to the “ON” setting.
c.Confirm that the
6.Verify optional VENT operation (if electric damper is installed):
a.Press and hold the “FAN” button until “ON” flashes on the display.
b.Release the “FAN” button, then press it again to switch fan operation to “AUTO”.
c.Press and hold the “VENT” button until “CLOSED” flashes on the display.
d. Release the “VENT” button, then press it again to switch vent mode to “OPEN”.
e. Confirm that the
f. Press and hold the “VENT” button until the “OPEN” flashes on the display.
g. Release the “VENT” button, then press it again to switch vent mode to “CLOSED”.
WARNING! DO NOT MAKE ANY OTHER CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.
7.Verify any additional optional control operations such as fan interlock or A/C lockout.
8.Proceed to the Operation section.
2.6 Troubleshooting
FOR THE HVAC PROFESSIONAL:
nNo display on initial start up.
Note: This is often the result of a drained capacitor. The capacitor will recharge once power is applied or
–Verify unit has power.
–Turn unit off then on.
–Disconnect the unit from power source then
nFunction not working properly.
– Verify wiring.
– Verify voltage with voltmeter.
nDehumidifier not working properly.
– See chart below:
| Wire connections | Operation |
| Yellow & Blue | Fan & Compressor |
| Yellow & Green | Fan Only |
|
|
|
DEH 3000R Dehumidifier & Ventilation System Controller | 5 | Installation, Operation & Service Manual |