All installations and services must be performed by qualified service personnel.
D. FAN AND LIMIT POSITION AND LOCATION
?WARNING: The predetermined fan and limit locations on all of the Thermo Pride oil fired furnaces have been tested and approved by Thermo Products, LLC. in conjunction with Underwriters Laboratories, Inc. Any attempt to relocate these safety controls or replace these safety controls with a control that is not approved, or is incompatible, may result in personal injury, substantial property damage or death.
The units listed in the table below must have the fan and limit control installed at the time of unit installation. A locating bracket is provided with each of the units below.
TABLE 2: Installation location of the fan and limit control for each furnace
Fig. 7: Fan and limit location for lowboys, horizontal units and highboys.
FAN & LIMIT LOCATION FOR HORIZONTAL UNITS WITH AIR CONDITIONING COIL:
The fan & limit control should be mounted between the
NOTE: The OL2, OC2 and OH2 only, come standard with an oil filter packaged with the furnace. This filter has the capacity of filtering down to a 10 micron particle. This is to assure the small diameter burner nozzles in the low heating capacity furnaces are installed with a fine filter to help prevent nozzle clogging.
E. BURNER INSTALLATION:
NOTICE: Remove all cardboard packing from around chamber before installing burner.
6