TOSHIBA

5.0 Operating the UPS

5.1

Operation Modes

 

 

 

 

5.1.3 Circuit-bypass mode

*Isolation only

UPS

 

 

 

 

 

Bypass circuit

for 1500 plus

receptacles

 

 

series (600VA)

(rear panel)

 

 

 

Power

 

 

 

 

input plug

Fuse

UPS

 

 

 

 

 

 

 

 

main

 

 

 

 

circuit

 

 

IEC-320

Input

 

Output

 

 

 

 

 

Transformer

 

Transformer

IEC-320

 

 

 

 

+

UPS batteries

= power flow

-

Power flow in circuit-bypass mode.

If the UPS unit is severely overloaded or develops an internal fault, the power flow is automatically switched from the unit's main circuit to the bypass circuit mode. Power flow through the bypass is shown in the above illustrations. This changeover occurs automatically in approximately 4 milliseconds. The switching period is not long enough to cause interruptions to occur in most UPS equipment loads.

The energy flow must be transferred manually from the UPS's bypass circuit back to the inverter circuit after first correcting the fault. Toggle the STOP/RUN switch (on the unit's front panel) first to STOP and then back to RUN. This procedure resets the UPS and transfers back to inverter. During circuit- bypass mode the AC-Input LED is ON, the On-Line LED is OFF, and the Fault LED may be ON or OFF.(See Section 9.2 Panel Layout).

5.2System Protection Features

The schematic shown below depicts the electrical locations of the protection devices on the UPS.

 

Input

Overcurrent

 

 

 

 

 

Abnormal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Isolation only

 

 

 

 

 

 

for 1500 plus

 

 

 

 

 

 

series (600VA)

 

Fuse

Rectifier/

 

 

 

Input

 

Inverter

 

Output

 

Charger/

 

 

 

Chopper

 

 

Output

 

 

 

 

 

 

 

 

Input

 

 

 

Output

 

 

Transformer

 

 

 

Transformer

 

 

 

 

+

 

 

 

 

 

 

Batteries

 

 

 

 

Low Battery

Overheating

Current Limit

Overvoltage/

 

 

Level

Overload

Undervoltage

 

 

 

 

5 - 2