4.0Specifications
4.1 Standard Series Specifications
| MODEL NUMBER |
| |||||
|
|
|
|
|
|
| |
|
|
| CAPACITY | 800 VA (0.56 kW) |
| 1000 VA (0.7 kW) | |
Input |
| Input voltage | Single phase, 220 Vac, +10% to | ||||
|
| Input frequency | 45 to 65 Hz |
|
|
| |
|
| Input capacity | 800 VA |
|
| 1000 VA | |
|
| Input power factor | Approximate unity (0.95 to 1.0) |
| |||
Battery | Battery rated voltage | 60 Vdc |
|
|
| ||
| Battery backup time when fully charged | 8 min. at full load (**) | 7 min. at full load (**) | ||||
| with 0.7 power factor at 77° F (25° C) | 20 min. at half load (**) | 18 min. at half load (**) | ||||
|
| Recharge time | Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***) | ||||
|
| Type | of batteries | Sealed |
|
|
|
Output |
| Output voltage |
| ||||
| Output | voltage regulation | Within +/- 3%, steady state |
| |||
|
| Output frequency | 50/60 Hz +/- 0.5% in | ||||
| Output | voltage waveform | |||||
|
|
|
| distortion with linear load |
| ||
| Rated load power factor | 0.7 lagging (0.6 to 1.0) |
| ||||
| Voltage transient characteristic | +/- 8% under 100% load step change | |||||
| Rated output current (rms) | 3.6A |
|
| 4.5A | ||
| Maximum output current (peak) | 10.8A |
|
| 13.5A | ||
| Inverter overload capacity | 150% for 30 seconds |
| ||||
|
|
| Crest factor | 3.0 |
|
|
|
Environment | Operating | temperature | 32 to 104° F (0 to 40° C), optimal | at 77° F (25° C) | |||
| Storage | temperature |
| ||||
| Operating humidity | 30 to 90%, no condensation |
| ||||
|
| Altitude(****) | Less than 3000 ft (1000 m) above sea level | ||||
| External | dimensions | 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm) | ||||
|
|
| Net weight | 58.8 lb (26.7 kg) | 60.7 lb (27.5 kg) | ||
|
| Acoustical noise | 50 dB at max. output, measured 3.3 ft (1 m) from front panel | ||||
| Efficiency | 85% |
|
| 87% | ||
Switches |
| Bypass switch | Automatic bypass is provided when the run switch is in the stop | ||||
|
|
|
| position, if a fault occurs, or if an | overload occurs (transfer time is | ||
|
|
|
| approximately 4 | msec) |
| |
Interfaces |
| IBM (TM) AS/400 |
|
|
|
| |
|
| LAN Manager | See section 6.0 | for details. |
| ||
| Fault detect and input power loss |
|
|
|
| ||
|
| RS232 ASCII |
|
|
|
| |
Options | Software for unattended |
|
|
|
| ||
| computer shutdown | Contact Toshiba for details on this option | |||||
| External | battery pack | Contact Toshiba for details on this option | ||||
|
|
|
|
|
|
|
|
(*) Output capacity reduced when input voltage is between
(**)Battery backup time may vary depending on the operating conditions including ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
4 - 1