TOSHIBA

4.0Specifications

4.1 Standard Series Specifications

 

MODEL NUMBER

UE1E1E008-5M

 

UE1E1E010-5M

 

 

 

 

 

 

 

 

 

 

CAPACITY

800 VA (0.56 kW)

 

1000 VA (0.7 kW)

Input

 

Input voltage

Single phase, 220 Vac, +10% to -30% (*)

 

 

Input frequency

45 to 65 Hz

 

 

 

 

 

Input capacity

800 VA

 

 

1000 VA

 

 

Input power factor

Approximate unity (0.95 to 1.0)

 

Battery

Battery rated voltage

60 Vdc

 

 

 

 

Battery backup time when fully charged

8 min. at full load (**)

7 min. at full load (**)

 

with 0.7 power factor at 77° F (25° C)

20 min. at half load (**)

18 min. at half load (**)

 

 

Recharge time

Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)

 

 

Type

of batteries

Sealed lead-acid

 

 

 

Output

 

Output voltage

Single-phase, 220 volts

 

 

Output

voltage regulation

Within +/- 3%, steady state

 

 

 

Output frequency

50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)

 

Output

voltage waveform

Computer-grade sine wave with less than 3.0% total harmonic

 

 

 

 

distortion with linear load

 

 

Rated load power factor

0.7 lagging (0.6 to 1.0)

 

 

Voltage transient characteristic

+/- 8% under 100% load step change

 

Rated output current (rms)

3.6A

 

 

4.5A

 

Maximum output current (peak)

10.8A

 

 

13.5A

 

Inverter overload capacity

150% for 30 seconds

 

 

 

 

Crest factor

3.0

 

 

 

Environment

Operating

temperature

32 to 104° F (0 to 40° C), optimal

at 77° F (25° C)

 

Storage

temperature

-4 to 104° F (-20 to 40° C)

 

 

Operating humidity

30 to 90%, no condensation

 

 

 

Altitude(****)

Less than 3000 ft (1000 m) above sea level

 

External

dimensions

8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)

 

 

 

Net weight

58.8 lb (26.7 kg)

60.7 lb (27.5 kg)

 

 

Acoustical noise

50 dB at max. output, measured 3.3 ft (1 m) from front panel

 

Efficiency (ac-dc-ac)

85%

 

 

87%

Switches

 

Bypass switch

Automatic bypass is provided when the run switch is in the stop

 

 

 

 

position, if a fault occurs, or if an

overload occurs (transfer time is

 

 

 

 

approximately 4

msec)

 

Interfaces

 

IBM (TM) AS/400

 

 

 

 

 

 

LAN Manager

See section 6.0

for details.

 

 

Fault detect and input power loss

 

 

 

 

 

 

RS232 ASCII

 

 

 

 

Options

Software for unattended

 

 

 

 

 

computer shutdown

Contact Toshiba for details on this option

 

External

battery pack

Contact Toshiba for details on this option

 

 

 

 

 

 

 

 

(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.

(**)Battery backup time may vary depending on the operating conditions including ambient temperature at the installation site.

(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used for battery backup.

(****) Above 3000 ft (1000 m), output capacity reduced.

4 - 1