TOSHIBA G3 APPLICATION GUIDELINE 21.5
Direction Change with RX Input (page 2 of 2)
Connections for bipolar reference
TERMINAL STRIP
ST  | CC  | F  | CC  | 
RX CC
bipolar reference
Example programming for bipolar reference
Group | Parameter  | New Value  | 
UTILITY PARAMETERS  | Blind Function Selection  | 1  | 
UTILITY PARAMETERS  | Frequency Setting Parameters Blind  | 1  | 
FREQUENCY SETTING PARAMETERS  | Frequency Priority Selection #1  | 3  | 
FREQUENCY SETTING PARAMETERS  | RX Terminal Standard or Adjustable  | 1  | 
FREQUENCY SETTING PARAMETERS  | RX Reference Setting Point #1  | |
FREQUENCY SETTING PARAMETERS  | RX Point #1 Frequency  | |
FREQUENCY SETTING PARAMETERS  | RX Reference Setting Point #2  | 100 (default)  | 
FREQUENCY SETTING PARAMETERS  | RX Point #2 Frequency  | 60  | 
NOTE: Never connect the ‘CC’ terminal to ground.
*For additional assistance, please contact Toshiba at (800)