E6581339⑥

3. Functional description

In this section, functions added by the installation of this expansion IO card option, on top of the standard inverter functions, are described.

*If the software version of inverter is less than V104, when OUT3 or OUT4 terminals is set as negative logic, it may output a flash pulse at inverter reset.

3.1Multi-function output terminal

Two output terminals and one relay output can be added. Function is similar to that of the output terminals of the inverter, so refer to the inverter instruction manual.

Parameter

Title

Function

 

Adjustment range

Default setting

f133

Output terminal function selection 4

(OUT3)

0 - 255

254

(Always OFF)

 

 

 

 

f134

Output terminal function selection 5

(OUT4)

0 - 255

254

(Always OFF)

 

 

 

 

f135

Output terminal function selection 6

(R1)

0 - 255

254

(Always OFF)

 

 

 

 

Monitor

Refer to the description on status monitor mode of inverter’s instruction manual.

The output terminal status can be monitored by the output terminal status parameter (fe07), and the parameter can be monitor by the serial communication.

fe07

bit No.

 

15

14

13

12

11

10

9

8

 

7

6

5

4

3

2

1

0

Symbol

 

---

 

---

 

---

 

---

 

---

 

---

 

---

 

 

R2

 

 

OUT

 

OUT

 

R1

OUT

OUT

FL

OUT

OUT

 

 

 

 

 

 

 

 

 

 

 

6

 

5

 

4

3

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: The OUT5, OUT6 and R2 are the terminal function of the expansion IO card option 2.

10

Page 11
Image 11
Toshiba ETB003Z instruction manual Functional description, Multi-function output terminal, Parameter, Monitor