E6581339⑥

3.4 External thermal trip input (TH1+, TH1-)

By connecting the thermistor to TH1+ and TH1- terminal, when the thermistor value is unusual, the inverter can be trip.

The resistor value

Detect condition

Movement

between TH1+ and TH1-

 

 

about under 70 ohm

Thermistor short broken detection

oh2 trip

about 70 - about 2.5k ohm

Normal value

―――

about 1.6k ohm

Thermistor fault reset

―――

about 3k ohm

Thermistor fault detection

oh2 trip

Parameter

Title

Function

Adjustment range

Default setting

f637 PTC thermal selection

0: Deselect

0

1: Select

 

 

 

 

Expansion IO card option

 

 

 

P15

PTC

TH1+

thermistor

 

 

TH1-

4.2k

Voltage

detection

circuit

12

Page 13
Image 13
Toshiba ETB003Z instruction manual External thermal trip input TH1+, TH1