E6581339⑥

3.2 Multi-function input terminal

Four output terminals can be added. Function is similar to that of the input terminals of the inverter, so refer to the inverter instruction manual.

Parameter

Title

Function

Adjustment range

Default setting

f119

Input terminal selection 9 (LI1)

0 - 135

0

f120

Input terminal selection 10 (LI2)

0 - 135

0

f121

Input terminal selection 11 (LI3)

0 - 135

0

f122

Input terminal selection 12 (LI4)

0 - 135

0

f144 *Input terminal 5~12 response time selection

2 - 200ms

8

* VF-PS1 does not have this parameter.

Monitor

Refer to the description on status monitor mode of inverter’s instruction manual.

The input terminal status can be monitored by the input terminal status parameter (fe06), and the parameter can be monitor by the serial communication.

fe06

bit No.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Symbol

LI8

 

LI7

 

LI6

 

LI5

 

LI4

LI3

LI2

LI1

S4

S3

S2

S1

RES

ST

R

F

Note: The LI5 ~ LI8 are the terminal function of the expansion IO card option 2.

3.3 -10V power supply

The frequency command can be input from RX terminal with pulse and negative voltage using N10(-10V) and PP(+10V) power.

PP (+10)

RX

2k ohm

N10 (-10V)

Inverter Terminal

Option Terminal

Potentio meter

Center position: 0V command

Pulse side position: +10V command

Negative side position: -10V command

The recommended wiring cable length is less than 1.5m with shielded cable.

11