Model LF620 and LF622 converters
Input signals
Analog signal — the voltage signal from detector, proportional to process flow rate (for LF622 separate type converter).
Digital input DI
Signal type: 20 to 30Vdc voltage signal
Input resistance: 2.7kΩ
Number of inputs: one point
Note: DI cannot be used with the Modbus communication.
DI function — One of the following functions can be assigned to the DI signal.
Range switching — Selects either the higher or lower range in the unidirectional or bidirectional
Totalizer control — ‘Starts and stops’ or ‘Rest and start’ the
Zero adjustment — Executes zero adjustment
Output signals
Current output:
Note: The current output cannot be used with the
(Refer table 6 for details)
Digital outputs — Two points are available as follows.
Digital output DO1:
Output type: Transistor open collector Number of outputs: One point
Output capacity: 30Vdc, 200mA maximum
Note: DO1 cannot be used if Modbus communication connection is 3 lines. (Refer table 6 for details)
Digital output DO2 :
Output type:
Output capacity: 150Vdc, 150mA maximum or 150Vac (peak to peak), 100mA maximum
Note: DO2 cannot be used with the Modbus communication. (Refer table 6 for details)
DO1 and DO2 functions — One of the following functions can be assigned to DO1 and/or DO2 .
•Pulse output (available only for DO1, DO2) Pulse rate: MAX 10kHz (10000pps)(DO1)
MAX 100Hz (100pps)(DO2)
(Over 1kpps,
Pulse width: 0.5 to 500ms (but less than half of the period for 100% flow rate)
Note: The same and simultaneous pulse is not available between DO1 and DO2.)
•
•High, High high, Low, and/or Low low alarm outputs (Note 2)
•Empty pipe alarm output (Note 2)
•Preset count output
•Converter failure alarm output
Note 1: Two outputs (DO1 and DO2) are needed for
Note 2: Normal Open (default set) or Normal Close is selected for alarm outputs when programming.
When power failure occurs, unit will be fault to Normal Open.
Communications output:
•HART (std.) — Digital signal is superimposed on
Conforms to HART protocol Load resistance: 240 to 750Ω Load capacitance: 0.25µF maximum Load inductance: 4mH maximum
•PROFIBUS (opt.)
Protocol:
Baud rate: 31.25kbps
Bus voltage:
Consumption electric current of bus: less than 16mA
Manufacture
Standard
Slave address:
Profile: Profile Ver.3.01 for Process Control Devices
Function blocks: AI(Flow)×1 , Totalizer×1
•MODBUS (opt.) Physical layer : RS485 Protocol : Modbus Mode : RTU
Baudrate : 4800, 9600, 19200bps
Data length : 8bit
Parity bit : None, Odd, Even
Stop bit : 1bit, 2bit
Error check :
Max. station number : 32(with Master device)
Max. cable length : 1.2km (Note)
Note: This length is specification of 3 line connection.
3