Outdoor Unit

3)Place unit on stand. Make sure it is level and fasten securely to the stand.

As shown in the figure below, install the foundation and vibration-proof rubber pads to directly support the bottom surface of the fixing leg that is in contact with the bottom plate of the outdoor unit.

When installing the foundation for an outdoor unit with downward piping, consider the piping work.

GOOD

Mounting leg

Foundation „For Reference

GOOD

Bottom plate

of outdoor unit

Foundation

Support the bottom surface of the mounting leg that is in contact with and underneath the bottom plate of the outdoor unit.

Installation Manual

Drain nipple

Waterproof rubber cap

(5pcs.)

Drain nipple

Waterproof rubber cap

„For Reference

If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is 32 °F (0 °C) or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the cabinet or fan.

If only the end of the mounting leg is supported, it may deform. NO GOOD

Foundation – 11 –Manual background

NO GOOD

 

Do not support

 

 

 

the outdoor unit

 

 

 

only with the

 

 

 

mounting leg.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When water is to be drained through the drain hose, attach the following drain nipple and waterproof rubber cap, and use the drain hose (Inner diameter: 0.6” (16 mm)) sold on the market. Also seal the screws securely with silicone material, etc., to prevent water from leaking.

Some conditions may cause condensation or dripping of water.

When collectively draining discharged water completely, use a drain pan.