Performance Data Cooling
4YCY4042A1 AT 1400 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 40.3 | 34.1 | 38.4 | 40.3 | 40.3 | 3.1 | |
85 | 63 | 42.0 | 27.7 | 31.9 | 36.2 | 39.0 | 3.1 | |
67 | 45.3 | 21.8 | 26.1 | 30.3 | 33.2 | 3.2 | ||
| ||||||||
| 71 | 48.9 | 15.9 | 20.2 | 24.4 | 27.3 | 3.2 | |
|
|
|
|
|
|
|
| |
| 59 | 37.6 | 32.9 | 37.2 | 37.6 | 37.6 | 3.4 | |
95 | 63 | 39.2 | 26.6 | 30.8 | 35.1 | 37.9 | 3.5 | |
67 | 42.2 | 20.7 | 24.9 | 29.2 | 32.0 | 3.5 | ||
| ||||||||
| 71 | 45.6 | 14.8 | 19.1 | 23.3 | 26.2 | 3.5 | |
|
|
|
|
|
|
|
| |
| 59 | 34.9 | 31.7 | 34.9 | 34.9 | 34.9 | 3.8 | |
105 | 63 | 36.4 | 25.4 | 29.7 | 33.9 | 36.4 | 3.8 | |
67 | 39.2 | 19.6 | 23.8 | 28.1 | 30.9 | 3.8 | ||
| ||||||||
| 71 | 42.3 | 13.7 | 18.0 | 22.2 | 25.1 | 3.8 | |
|
|
|
|
|
|
|
| |
| 59 | 32.2 | 30.5 | 32.2 | 32.2 | 32.2 | 4.1 | |
115 | 63 | 33.6 | 24.3 | 28.6 | 32.8 | 33.6 | 4.1 | |
67 | 36.2 | 18.5 | 22.7 | 26.9 | 29.8 | 4.2 | ||
| ||||||||
| 71 | 39.0 | 12.6 | 16.8 | 21.1 | 23.9 | 4.2 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 1225 | 0.97 |
| 0.98 |
HIGH | 1575 | 1.03 |
| 1.02 |
|
|
| ||
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
1360 | 42000 |
| 14.25 | 12.00 |
|
|
|
|
|
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
4YCY4048A1/3 AT 1600 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 45.3 | 38.2 | 42.9 | 45.3 | 45.3 | 3.6 | |
85 | 63 | 47.2 | 31.0 | 35.7 | 40.5 | 43.7 | 3.6 | |
67 | 50.9 | 24.4 | 29.1 | 33.9 | 37.1 | 3.7 | ||
| ||||||||
| 71 | 55.0 | 17.7 | 22.5 | 27.3 | 30.4 | 3.7 | |
| 59 | 42.7 | 37.0 | 41.7 | 42.7 | 42.7 | 3.9 | |
95 | 63 | 44.5 | 29.8 | 34.6 | 39.3 | 42.6 | 4.0 | |
67 | 48.0 | 23.2 | 28.0 | 32.8 | 36.0 | 4.0 | ||
| ||||||||
| 71 | 51.8 | 16.7 | 21.4 | 26.2 | 29.4 | 4.0 | |
| 59 | 40.1 | 35.8 | 40.1 | 40.1 | 40.1 | 4.3 | |
105 | 63 | 41.8 | 28.7 | 33.5 | 38.3 | 41.4 | 4.4 | |
67 | 45.0 | 22.2 | 27.0 | 31.7 | 34.9 | 4.4 | ||
| ||||||||
| 71 | 48.6 | 15.6 | 20.4 | 25.1 | 28.3 | 4.4 | |
| 59 | 37.5 | 34.7 | 37.5 | 37.5 | 37.5 | 4.7 | |
115 | 63 | 39.1 | 27.7 | 32.4 | 37.2 | 39.1 | 4.7 | |
67 | 42.1 | 21.1 | 25.8 | 30.6 | 33.8 | 4.8 | ||
| ||||||||
| 71 | 45.5 | 14.5 | 19.3 | 24.0 | 27.2 | 4.8 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 1400 | 0.97 |
| 0.98 |
HIGH | 1800 | 1.03 |
| 1.02 |
|
|
| ||
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
1605 | 48000 |
| 14.20 | 11.90 |
|
|
|
|
|
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
4YCY4060A1/3 AT 2000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 56.5 | 47.6 | 53.5 | 56.5 | 56.5 | 4.4 | |
85 | 63 | 58.9 | 38.5 | 44.5 | 50.5 | 54.4 | 4.4 | |
67 | 63.5 | 30.2 | 36.2 | 42.2 | 46.2 | 4.5 | ||
| ||||||||
| 71 | 68.5 | 21.9 | 27.8 | 33.8 | 37.8 | 4.5 | |
| 59 | 53.1 | 46.0 | 52.0 | 53.1 | 53.1 | 4.8 | |
95 | 63 | 55.4 | 37.0 | 43.1 | 49.0 | 53.0 | 4.9 | |
67 | 59.7 | 28.8 | 34.8 | 40.7 | 44.8 | 5.0 | ||
| ||||||||
| 71 | 64.4 | 20.5 | 26.4 | 32.4 | 36.4 | 5.0 | |
| 59 | 49.7 | 44.5 | 49.7 | 49.7 | 49.7 | 5.3 | |
105 | 63 | 51.9 | 35.7 | 41.6 | 47.6 | 51.6 | 5.3 | |
67 | 55.9 | 27.4 | 33.3 | 39.3 | 43.3 | 5.4 | ||
| ||||||||
| 71 | 60.3 | 19.1 | 25.0 | 31.0 | 35.0 | 5.4 | |
| 59 | 46.4 | 43.0 | 46.4 | 46.4 | 46.4 | 5.8 | |
115 | 63 | 48.3 | 34.2 | 40.2 | 46.2 | 48.3 | 5.8 | |
67 | 52.1 | 26.0 | 32.0 | 37.9 | 41.9 | 5.9 | ||
| ||||||||
| 71 | 56.2 | 17.7 | 23.7 | 29.6 | 33.7 | 5.9 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 1750 | 0.97 |
| 0.98 |
HIGH | 2250 | 1.03 |
| 1.02 |
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
1799 | 58500 |
| 14.00 | 11.90 |
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.