Performance Data Cooling
4YCY4030A1 AT 1000 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 29.8 | 24.1 | 26.9 | 29.2 | 28.9 | 2.3 | |
85 | 63 | 31.0 | 19.7 | 22.6 | 25.5 | 27.4 | 2.3 | |
67 | 33.4 | 15.8 | 18.6 | 21.5 | 23.4 | 2.3 | ||
| ||||||||
| 71 | 36.1 | 11.8 | 14.6 | 17.5 | 19.4 | 2.3 | |
| 59 | 27.3 | 23.0 | 25.8 | 27.3 | 27.3 | 2.5 | |
95 | 63 | 28.5 | 18.7 | 21.5 | 24.4 | 26.3 | 2.5 | |
67 | 30.7 | 14.7 | 17.6 | 20.4 | 22.3 | 2.5 | ||
| ||||||||
| 71 | 33.1 | 10.7 | 13.6 | 16.5 | 18.4 | 2.5 | |
|
|
|
|
|
|
|
| |
| 59 | 24.8 | 21.9 | 24.7 | 24.8 | 24.8 | 2.7 | |
105 | 63 | 25.9 | 17.6 | 20.5 | 23.3 | 25.2 | 2.7 | |
67 | 27.9 | 13.7 | 16.5 | 19.4 | 21.3 | 2.7 | ||
| ||||||||
| 71 | 30.1 | 9.7 | 12.6 | 15.4 | 17.4 | 2.7 | |
|
|
|
|
|
|
|
| |
| 59 | 22.4 | 20.8 | 22.4 | 22.4 | 22.4 | 2.9 | |
115 | 63 | 23.3 | 16.6 | 19.5 | 22.3 | 23.3 | 2.9 | |
67 | 25.1 | 12.7 | 15.5 | 18.4 | 20.3 | 2.9 | ||
| ||||||||
| 71 | 27.1 | 8.7 | 11.6 | 14.4 | 16.4 | 2.9 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 875 | 0.97 |
| 0.98 |
HIGH | 1125 | 1.03 |
| 1.02 |
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
890 | 30000 |
| 14.00 | 12.00 |
|
|
|
|
|
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
4YCY4024A1 AT 800 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 22.9 | 19.1 | 21.4 | 22.9 | 22.9 | 1.8 | |
85 | 63 | 23.9 | 15.6 | 17.9 | 20.2 | 21.8 | 1.8 | |
67 | 25.8 | 12.3 | 14.7 | 17.0 | 18.6 | 1.9 | ||
| ||||||||
| 71 | 27.8 | 9.1 | 11.5 | 13.8 | 15.3 | 1.9 | |
| 59 | 20.9 | 18.2 | 20.5 | 20.9 | 20.9 | 2.0 | |
95 | 63 | 21.8 | 14.7 | 17.0 | 19.3 | 20.9 | 2.0 | |
67 | 23.5 | 11.5 | 13.8 | 16.1 | 17.7 | 2.0 | ||
| ||||||||
| 71 | 25.3 | 8.3 | 10.6 | 12.9 | 14.5 | 2.0 | |
| 59 | 18.8 | 17.3 | 18.8 | 18.8 | 18.8 | 2.1 | |
105 | 63 | 19.6 | 13.8 | 16.1 | 18.5 | 19.6 | 2.1 | |
67 | 21.1 | 10.6 | 12.9 | 15.3 | 16.8 | 2.2 | ||
| ||||||||
| 71 | 22.8 | 7.4 | 9.7 | 12.1 | 13.6 | 2.2 | |
| 59 | 16.7 | 16.4 | 16.7 | 16.7 | 16.7 | 2.3 | |
115 | 63 | 17.5 | 13.0 | 15.3 | 17.5 | 17.5 | 2.3 | |
67 | 18.8 | 9.8 | 12.1 | 14.4 | 16.0 | 2.3 | ||
| ||||||||
| 71 | 20.3 | 6.6 | 8.9 | 11.2 | 12.8 | 2.3 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 700 | 0.97 |
| 0.98 |
HIGH | 900 | 1.03 |
| 1.02 |
|
|
| ||
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
790 | 23400 |
| 14.00 | 11.60 |
|
|
|
|
|
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
4YCY4036A1/3 AT 1200 NOM CFM (COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES)
OD | ID | TOT | SENS CAP AT ENTERING DB TEMP | TOTAL | ||||
AMB | WB | CAP | 72 | 75 | 78 | 80 | KW | |
| 59 | 34.5 | 28.8 | 32.4 | 34.5 | 34.5 | 2.7 | |
85 | 63 | 36.0 | 23.4 | 27.0 | 30.5 | 32.9 | 2.7 | |
67 | 38.8 | 18.5 | 22.0 | 25.6 | 27.9 | 2.8 | ||
| ||||||||
| 71 | 41.9 | 13.5 | 17.1 | 20.6 | 23.0 | 2.8 | |
| 59 | 32.0 | 27.6 | 31.2 | 32.0 | 32.0 | 3.0 | |
95 | 63 | 33.4 | 22.3 | 25.9 | 29.4 | 31.8 | 3.1 | |
67 | 35.9 | 17.4 | 20.9 | 24.5 | 26.9 | 3.1 | ||
| ||||||||
| 71 | 38.8 | 12.4 | 16.0 | 19.6 | 21.9 | 3.1 | |
| 59 | 29.5 | 26.5 | 29.5 | 29.5 | 29.5 | 3.3 | |
105 | 63 | 30.7 | 21.2 | 24.8 | 28.4 | 30.7 | 3.4 | |
67 | 33.1 | 16.3 | 19.9 | 23.4 | 25.8 | 3.4 | ||
| ||||||||
| 71 | 35.7 | 11.4 | 15.0 | 18.5 | 20.9 | 3.4 | |
| 59 | 26.9 | 25.4 | 26.9 | 26.9 | 26.9 | 3.6 | |
115 | 63 | 28.1 | 20.2 | 23.7 | 27.3 | 28.1 | 3.7 | |
67 | 30.2 | 15.3 | 18.8 | 22.4 | 24.8 | 3.7 | ||
| ||||||||
| 71 | 32.7 | 10.4 | 13.9 | 17.5 | 19.9 | 3.7 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
| AIR FLOW | CAPACITY |
| TOTAL POWER |
| RATE, CFM | MULTIPLIER |
| MULTIPLIER |
LOW | 1050 | 0.97 |
| 0.98 |
HIGH | 1350 | 1.03 |
| 1.02 |
| ARI RATING FOR COOLING |
| ||
CFM | CAPACITY (A) TEST | SEER | EER | |
1210 | 36000 |
| 14.20 | 11.60 |
ARI Standard Capacity Rating Conditions
ARI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering outdoor coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
9