Trane 4YCY4024A, 4YCY4060A manual General Data

Models: 4YCY4024A 4YCY4060A

1 29
Download 29 pages 59.65 Kb
Page 5
Image 5
General Data

General Data

MODEL

4YCY4024A1064A

4YCY4030A1075A

4YCY4036A1075A

4YCY4036A1096A

RATED Volts/PH/Hz

 

208-230/1/60

208-230/1/60

208-230/1/60

208-230/1/60

 

 

Performance Cooling BTUH￿

 

23400

30000

36000

36000

 

 

Indoor Airflow (CFM)

 

790

900

1210

1210

 

 

Power Input (KW)

 

2.162

2.5

3.284

3.284

 

 

EER/SEER(BTU/Watt-Hr.)￿

 

11.6 / 14.0

12.0 / 14.0

11.6 / 14.2

11.6 / 14.2

 

 

Sound Power Rating [dB(A)]8

 

68

71

69

69

 

 

Performance Heating￿

 

48000

56250

56250

72000

 

 

Input BTUH - 1st Stage (Natural Gas)￿

 

 

Input BTUH - 2nd Stage (Natural Gas)￿

64000

75000

75000

96000

 

 

AFUE

 

79.0

79.5

79.5

80.0

 

 

Temp. Rise — Min/Max (°F)

 

35 / 65

30 / 60

30 / 60

40 / 70

 

 

Orifice Qty / Drill Size (Natural Gas)￿

2 / #37

2 / #33

2 / #33

3 / #37

 

 

POWER CONN.—V/PH/HZ

 

208-230/1/60

208-230/1/60

208-230/1/60

208-230/1/60

 

 

Min. Brch. Cir. Ampacity￿

 

16.5

19.2

24.6

24.6

 

 

Fuse Size — Max. (amps)

 

25

30

40

40

 

 

Fuse Size — Recmd. (amps)

 

25

30

40

40

 

 

COMPRESSOR

RECIPROCATING

RECIPROCATING

SCROLL

SCROLL

Volts/Ph/Hz

 

208-230/1/60

200-230/1/60

208-230/1/60

208-230/1/60

 

 

R.L. Amps — L.R. Amps

 

8.3 / 57.8

11.1 / 63

15.4 / 83

15.4 / 83

 

 

OUTDOOR COIL — TYPE

 

SPINE-FIN

SPINE-FIN

SPINE-FIN

SPINE-FIN

 

Rows/F.P.I.

 

2 / 24

2 / 24

2 / 24

2 / 24

 

 

Face Area (sq.ft.)

 

13.32

15.49

15.49

15.49

 

 

Tube Size (in.)

 

3/8

3/8

3/8

3/8

 

 

INDOOR COIL — TYPE

 

PLATE FIN

PLATE FIN

PLATE FIN

PLATE FIN

 

Rows/F.P.I.

 

3 / 15

3 / 15

4 / 15

4 / 15

 

 

Face Area (sq.ft.)

 

3.54

3.54

3.54

3.54

 

 

Tube Size (in.)

 

3/8

3/8

3/8

3/8

 

 

Refrigerant Control

EXPANSION VALVE

EXPANSION VALVE

EXPANSION VALVE

EXPANSION VALVE

Drain Conn. Size (in.)

3/4 FEMALE NPT

3/4 FEMALE NPT

3/4 FEMALE NPT

3/4 FEMALE NPT

OUTDOOR FAN — TYPE

 

PROPELLER

PROPELLER

PROPELLER

PROPELLER

 

Dia. (in.)

 

23.4

23.4

23.4

23.4

 

 

Drive/No. Speeds

 

DIRECT / 1

DIRECT / 1

DIRECT / 1

DIRECT / 1

Motor — HP/R.P.M.

 

1/12 / 810

1/6 / 830

1/5 / 830

1/5 / 830

 

 

Volts/Ph/Hz

 

208-230/1/60

208-230/1/60

208-230/1/60

208-230/1/60

 

 

F.L. Amps/L.R. Amps

 

0.54 / 0.95

1.0 / 1.7

1.1 / 1.9

1.1 / 1.9

 

 

INDOOR FAN — TYPE

 

CENTRIFUGAL

CENTRIFUGAL

CENTRIFUGAL

CENTRIFUGAL

 

Dia x Width (in.)

 

10 X 10

10 X 10

10 X 10

10 X 10

Drive/No. Speeds

DIRECT / VARIABLE

DIRECT / VARIABLE

DIRECT / VARIABLE

DIRECT / VARIABLE

CFM @ 0.0 in. w.g.￿

SEE FAN PERF TABLE

SEE FAN PERF TABLE

SEE FAN PERF TABLE

SEE FAN PERF TABLE

Motor — HP/R.P.M.

 

1/2 / VARIABLE

1/2 / VARIABLE

1/2 / VARIABLE

1/2 / VARIABLE

Volts/Ph/Hz

 

200-230/1/60

208-230/1/60

200-230/1/60

200-230/1/60

 

 

F.L. Amps/L.R. Amps

 

4.3 / 4.3

4.3 / 4.3

4.3 / 4.3

4.3 / 4.3

 

 

COMBUSTION FAN — TYPE

 

CENTRIFUGAL

CENTRIFUGAL

CENTRIFUGAL

CENTRIFUGAL

 

Drive/No. Speeds

 

DIRECT / 2

DIRECT / 2

DIRECT / 2

DIRECT / 2

Motor — HP/R.P.M.

1/45 / 2800/1500

1/45 / 2800/1500

1/45 / 2800/1500

1/45 / 2800/1500

 

 

Volts/Ph/Hz

 

208-230/1/60

208-230/1/60

208-230/1/60

208-230/1/60

 

 

FLA

 

0.34

0.34

0.34

0.34

 

 

FILTER / FURNISHED

 

NO

NO

NO

NO

 

Type Recommended

 

THROWAWAY

THROWAWAY

THROWAWAY

THROWAWAY

Recmd. Face Area (sq. ft.)￿

 

4.0

4.0

4.0

4.0

 

 

REFRIGERANT

 

R410A

R410A

R410A

R410A

 

Charge (lbs.)￿

 

5.8

6.0625

6.75

6.75

 

 

GAS PIPE SIZE (in.)

 

1/2

1/2

1/2

1/2

 

 

DIMENSIONS

 

H X W X L

H X W X L

H X W X L

H X W X L

 

Crated (in.)

45.86 / 44.5 / 52.03

45.86 / 44.5 / 52.03

47.86 / 44.5 / 52.03

47.86 / 44.5 / 52.03

 

 

WEIGHT

 

481 / 385

481 / 385

488 / 392

493 / 397

 

 

Shipping (lbs.) / Net (lbs.)

 

 

 

1Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240. Noise calculated in accordance with A.R.I. Standard 270.

2All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a rate of 4% per 1000 ft. elevation.

3Convertible to LPG.

4This value is approximate. For more precise value, see Unit Nameplate.

5Based on U.S. Government Standard Tests.

6Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C.

7Unit is shipped on high input, unit is convertible to low input with a Low Fire accessory kit.

8Sound Power values are not adjusted for ARI 270-95 tonal corrections.