GAF2A0A18 AIRFLOW PERFORMANCE TABLE

General

Data

GAF2A0A18 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE

GAF2A0A18S11SA

EXTERNAL STATIC

 

 

AIRFLOW (CFM)

 

 

(in w.g)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed Taps - 230 VOLTS

Speed Taps - 208 VOLTS

 

 

 

 

 

 

 

 

3

2 †

1

3

2 †

1

 

 

 

 

 

 

 

0

952

768

710

940

654

598

 

 

 

 

 

 

 

0.1

894

741

687

885

636

581

 

 

 

 

 

 

 

0.2

845

704

658

831

610

558

 

 

 

 

 

 

 

0.3

785

662

620

775

577

526

 

 

 

 

 

 

 

0.4

724

607

568

714

529

477

 

 

 

 

 

 

 

0.5

652

531

494

640

460

415

 

 

 

 

 

 

 

0.6

557

441

404

543

378

347

 

 

 

 

 

 

 

0.7

428

346

N/A

418

244

N/A

 

 

 

 

 

 

 

0.8

284

N/A

N/A

225

N/A

N/A

 

 

 

 

 

 

 

0.9

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

1.0

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

NOTES:

1.Values are with wet coil and without filters.

2.Contact your particular filter manufacturer for pressure drop data.

3.Electric heater pressure drop is negligible and is included within the airflow data.

4.† Factory Setting

GAF2A0A18S11SA MINIMUM HEATER AIRFLOW CFM

Heater

Minimum Air Speed Tap

 

 

 

 

Without Heat Pump

With Heat Pump

 

 

 

BAYECAA05LG1AA

Tap 1

Tap 3

 

 

 

BAYECAA08LG1AA

Available soon

Available soon

 

 

 

BAYECAA10LG1AA

Available soon

Available soon

 

 

 

SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS

Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.