Performance
Data
GAF2A0A24 AIRFLOW PERFORMANCE TABLE
AIRFLOW PERFORMANCE
GAF2A0A24S21SA
EXTERNAL STATIC |
|
| AIRFLOW (CFM) |
|
| |
(in w.g) |
|
|
|
| ||
|
|
|
|
|
| |
| Speed Taps - 230 VOLTS | Speed Taps - 208 VOLTS | ||||
|
|
|
|
|
|
|
| 3 | 2 † | 1 | 3 | 2 † | 1 |
|
|
|
|
|
|
|
0 | 998 | 848 | 771 | 899 | 737 | 658 |
|
|
|
|
|
|
|
0.1 | 949 | 816 | 745 | 868 | 710 | 630 |
|
|
|
|
|
|
|
0.2 | 911 | 784 | 711 | 834 | 683 | 602 |
|
|
|
|
|
|
|
0.3 | 869 | 750 | 679 | 794 | 650 | 567 |
|
|
|
|
|
|
|
0.4 | 825 | 708 | 638 | 756 | 611 | 524 |
|
|
|
|
|
|
|
0.5 | 772 | 659 | 586 | 704 | 547 | 476 |
|
|
|
|
|
|
|
0.6 | 707 | 591 | 518 | 641 | 499 | 415 |
|
|
|
|
|
|
|
0.7 | 614 | 513 | 444 | 555 | 420 | 346 |
|
|
|
|
|
|
|
0.8 | 533 | 416 | 356 | 465 | 339 | 268 |
|
|
|
|
|
|
|
0.9 | 413 | 309 | 218 | 351 | 203 | 138 |
|
|
|
|
|
|
|
1.0 | 241 | 130 | N/A | 167 | N/A | N/A |
|
|
|
|
|
|
|
NOTES:
1.Values are with wet coil and without filters.
2.Contact your particular filter manufacturer for pressure drop data.
3.Electric heater pressure drop is negligible and is included within the airflow data.
4.† Factory Setting
GAF2A0A24S21SA MINIMUM HEATER AIRFLOW CFM
Heater | Minimum Air Speed Tap | |
|
|
|
| Without Heat Pump | With Heat Pump |
|
|
|
BAYECAA05LG1AA | Tap 1 | Tap 2 |
|
|
|
BAYECAA08LG1AA | Available soon | Available soon |
|
|
|
BAYECAA10LG1AA | Available soon | Available soon |
|
|
|
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.
8 | Pub. No. |