Trane GAF2A0A36S31SA, GAF2A0A24S21SA manual Performance Data, GAF2A0A24 AIRFLOW PERFORMANCE TABLE

Models: GAF2A0A36S31SA GAF2A0A30S21SA GAF2A0A24S21SA

1 20
Download 20 pages 34.54 Kb
Page 8
Image 8
Performance

Performance

Data

GAF2A0A24 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE

GAF2A0A24S21SA

EXTERNAL STATIC

 

 

AIRFLOW (CFM)

 

 

(in w.g)

 

 

 

 

 

 

 

 

 

 

 

Speed Taps - 230 VOLTS

Speed Taps - 208 VOLTS

 

 

 

 

 

 

 

 

3

2 †

1

3

2 †

1

 

 

 

 

 

 

 

0

998

848

771

899

737

658

 

 

 

 

 

 

 

0.1

949

816

745

868

710

630

 

 

 

 

 

 

 

0.2

911

784

711

834

683

602

 

 

 

 

 

 

 

0.3

869

750

679

794

650

567

 

 

 

 

 

 

 

0.4

825

708

638

756

611

524

 

 

 

 

 

 

 

0.5

772

659

586

704

547

476

 

 

 

 

 

 

 

0.6

707

591

518

641

499

415

 

 

 

 

 

 

 

0.7

614

513

444

555

420

346

 

 

 

 

 

 

 

0.8

533

416

356

465

339

268

 

 

 

 

 

 

 

0.9

413

309

218

351

203

138

 

 

 

 

 

 

 

1.0

241

130

N/A

167

N/A

N/A

 

 

 

 

 

 

 

NOTES:

1.Values are with wet coil and without filters.

2.Contact your particular filter manufacturer for pressure drop data.

3.Electric heater pressure drop is negligible and is included within the airflow data.

4.† Factory Setting

GAF2A0A24S21SA MINIMUM HEATER AIRFLOW CFM

Heater

Minimum Air Speed Tap

 

 

 

 

Without Heat Pump

With Heat Pump

 

 

 

BAYECAA05LG1AA

Tap 1

Tap 2

 

 

 

BAYECAA08LG1AA

Available soon

Available soon

 

 

 

BAYECAA10LG1AA

Available soon

Available soon

 

 

 

SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS

Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.