Trane GAF2A0A24S21SA manual GAF2A0A30 AIRFLOW PERFORMANCE TABLE, Performance Data, External Static

Models: GAF2A0A36S31SA GAF2A0A30S21SA GAF2A0A24S21SA

1 20
Download 20 pages 34.54 Kb
Page 9
Image 9
GAF2A0A30 AIRFLOW PERFORMANCE TABLE

Performance

Data

GAF2A0A30 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE

GAF2A0A30S21SA

EXTERNAL STATIC

 

 

 

 

 

 

(in w.g)

 

 

 

 

 

 

 

Speed Taps - 230 VOLTS

Speed Taps - 208 VOLTS

 

 

 

 

 

 

 

 

3

2 †

1

3

2

1

 

 

 

 

 

 

 

0

1052

967

932

1024

877

826

 

 

 

 

 

 

 

0.1

1012

929

898

980

846

800

 

 

 

 

 

 

 

0.2

963

888

861

934

814

771

 

 

 

 

 

 

 

0.3

914

849

823

885

777

738

 

 

 

 

 

 

 

0.4

865

805

784

837

739

703

 

 

 

 

 

 

 

0.5

816

759

741

788

697

663

 

 

 

 

 

 

 

0.6

759

698

681

739

640

602

 

 

 

 

 

 

 

0.7

690

622

592

668

559

515

 

 

 

 

 

 

 

0.8

589

503

463

559

423

395

 

 

 

 

 

 

 

0.9

389

336

318

375

285

259

 

 

 

 

 

 

 

1.0

179

149

119

175

NA

NA

 

 

 

 

 

 

 

NOTES:

1.Values are with wet coil and without filters.

2.Contact your particular filter manufacturer for pressure drop data.

3.Electric heater pressure drop is negligible and is included within the airflow data.

4.† Factory Setting

GAF2A0A30S21SA MINIMUM HEATER AIRFLOW CFM

Heater

Minimum Air Speed Tap

 

 

 

 

Without Heat Pump

With Heat Pump

 

 

 

BAYECAA05LG1AA

Tap 1

Tap 1

 

 

 

BAYECAA08LG1AA

Available soon

Available soon

 

 

 

BAYECAA10LG1AA

Available soon

Available soon

 

 

 

SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS

Note: Heating and cooling speeds are the same, factory set at Speed Tap #2.

Pub. No. 22-1858-02

9

Page 9
Image 9
Trane GAF2A0A24S21SA manual GAF2A0A30 AIRFLOW PERFORMANCE TABLE, Performance Data, AIRFLOW PERFORMANCE GAF2A0A30S21SA