![](/images/new-backgrounds/1055321/55321157x1.webp)
|
|
| Installation - Electrical |
|
|
|
|
| |
Table 21 | Alarm and Status Relay Output Configuration Table |
| ||
|
|
|
| |
|
| Description |
| |
Alarm Ckt 1 |
| This output is true whenever there is any diagnostic effecting Refrigerant Circuit 1, whether latching or |
| |
|
| automatically clearing, including diagnostics affecting the entire chiller. This classification does not |
| |
|
| include informational diagnostics. |
| |
Alarm Ckt 2 |
| This output is true whenever there is any diagnostic affecting Refrigerant Circuit 2 whether latching or |
| |
|
| automatically clearing, including diagnostics effecting the entire chiller. This classification does not |
| |
|
| include informational diagnostics. |
| |
Chiller Limit Mode | This output is true whenever the chiller has been running in one of the Unloading types of limit modes |
|
(with a 20 minute fil- (Condenser, Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes. ter)
Circuit 1 Running | This output is true whenever any compressors are running (or commanded to be running) on Refrigerant | |||
| Circuit 1, and false when no compressors are commanded to be running on that circuit. | |||
Circuit 2 Running | This output is true whenever any compressors are running (or commanded to be running) on Refrigerant | |||
| Circuit 2, and false when no compressors are commanded to be running on that circuit. | |||
Chiller Running | This output is true whenever any compressors are running (or commanded to be running) on the chiller | |||
| and false when no compressors are commanded to be running on the chiller. | |||
Maximum Capacity | This output is true whenever the chiller has reached maximum capacity or had reached its maximum | |||
(software 18.0 or | capacity and since that time has not fallen below 70% average current relative to the rated ARI current | |||
later) | for the chiller. The output is false when the chiller falls below 70% average current and, since that time, | |||
| had not reestablished maximum capacity. |
| ||
|
| Relay Assignments Using TechView |
| |
|
| CH530 Service Tool (TechView) is used to install the Alarm and Status Relay Option | ||
|
| package and assign any of the above list of events or status to each of the four relays | ||
|
| provided with the option. The relays to be programmed are referred to by the relay’s | ||
|
| terminal numbers on the LLID board 1U12. |
| |
|
| The default assignments for the four available relays of the RTAC Alarm and Status | ||
|
| Package Option are: |
| |
|
| Table 22 | Default Assignments |
|
|
|
|
|
|
|
| Relay |
|
|
|
| Relay 1 Terminals J2 | Alarm | |
|
| Relay 2 Terminals J2 - 9,8,7: | Chiller Running | |
|
| Relay 3 Terminals | Maximum Capacity (software 18.0 or later) | |
|
| Relay 4 Terminals | Chiller Limit |
If any of the Alarm/Status relays are used, provide electrical power, 115 VAC with
Low Voltage Wiring
The remote devices described below require low voltage wiring. All wiring to and from these remote input devices to the Control Panel must be made with shielded, twisted pair conductors. Be sure to ground the shielding only at the panel.
To prevent control malfunctions, do not run low voltage wiring (<30 V) in conduit with conductors carrying more than 30 volts.
Emergency Stop
CH530 provides auxiliary control for a customer specified/installed latching trip out. When this
Connect low voltage leads to terminal strip locations on 1U4. Refer to the field diagrams that are shipped with the unit.
| 79 |