MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

2-11

Terminals 33 to 34, 35 to 36 "Minor Fault” contact (OUT8)

Activated when a minor fault has occurred to the system.

Terminals 37 to 38, 39 to 40 "Total Alarm” contact (OUT9)

Activated when an alarm, a minor fault, or a major fault has occurred to the system.

NOTE: The UPS is equipped with a selectable output contact feature. The above alarms are the default settings. Contact MITSUBISHI ELECTRIC AUTOMATION, INC. for setup information.

B)Input Contacts (for remote access of UPS)

External contacts are provided by the user of the UPS system. Terminal voltage at the UPS is 24Vdc. Provide external dry contact accordingly.

NOTE: Do not apply voltages to remote access input terminals. Damage to UPS may result.

Refer to Figure 2.17 for a typical wiring configuration. Although this figure applies to the remote start/stop terminals, the same wiring arrangement is used for emergency stop; battery liquid low; and battery temperature high.

FIGURE 2.17 Remote "Start" Contact Connections

UPS Cabinet

External to UPS

 

Cabinet

 

Relay

Start

 

Coil

Start

 

 

 

 

Switch

 

Common

4S

 

0.5S -

24 VDC

ON

 

OFF

 

Relay Coil current : 8.3mA

Use Momentary Switches Only

 

User supplied

Details of input contacts for remote access : TN2

Terminals 1 to 2 Remote "Inverter Start" input terminal (IN1)

Used to start inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

Terminals 3 to 4 Remote "Inverter Stop" input terminal (IN2)

Used to stop inverter from a remote location. UPS must be programmed for remote operation. Refer to Operations Menu for procedure.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 30
Image 30
Mitsubishi 2033D SERIES Terminals 33 to 34, 35 to 36 Minor Fault contact OUT8, Input Contacts for remote access of UPS