E)External Battery Supply
Please refer to the following when installing and maintaining batteries:
1.The customer shall refer to the battery manufacturer's installation manual for battery installation and maintenance instructions.
2.The maximum permitted fault current from the remote battery supply, and the DC voltage rating of the battery supply
TABLE 3.4 Maximum Permitted Fault Current
UPS CAPACITY | DC VOLTAGE | MAXIMUM PERMITTED |
(kVA) | RATING (V) | FAULT CURRENT (A) |
|
|
|
30 | 480 | 25000 |
50 | 480 | 25000 |
80 | 480 | 25000 |
3.3Procedure for Cable Connections *
i.Confirm the capacity of the UPS being installed. Identify the input/output power terminal blocks as shown in the appropriate Figures
ii.Connect the grounding conductor from the input service entrance to the UPS ground bar.
*Wire per local and/or national code.
iii.Two (2) sources feeding the UPS:
(1)Connect the converter input power cables from the input service entrance to the converter input power terminals, identified as A, B, C in Figures
(2)Confirm that an external bypass input circuit breaker (MCCB) is installed (refer to WARNING 2, page
(3)Referring to Figures
(4)Connect the external signal terminal block as desired. Refer to section 2.5 and Figure
2.15for functional description. 12 AWG, or less, shielded conductor is recommended.