MITSUBISHI

 

2033D SERIES UPS

Page Number:

 

ELECTRIC

OWNERS / TECHNICAL MANUAL

6-3

 

 

 

 

 

 

 

 

 

 

(Note 9)

 

 

 

 

(Note 1)

(Note 2)

(Note 3)

Code

Status message

 

Contents

Guidance

Buzzer

External

Failure

indication

 

 

 

 

 

send-out

lamp

 

 

 

 

 

 

contact

 

UF213

INV. OR CONV.

 

Overheating of main circuit parts

CALL SERVICE

[1]

Major

Lit on

OVERTEMPERATURE

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF214

COOLING FAN

 

Abnormality of cooling fan inside panel

CALL SERVICE

[1]

Major

Lit on

ABNORMAL

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF255

52C ABNORMAL

 

52C turned OFF during inverter power

CALL SERVICE

[2]

Minor

Flicker

 

supply

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF256

OUTPUT VOLTAGE

 

Inverter output voltage fell out of +/- 5%

CALL SERVICE

[2]

Minor

Flicker

ABNORMAL

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF258

LOAD ABNORMAL

 

More than 4 overcurrent transfers in 5

CALL SERVICE

[2]

Minor

Flicker

 

minutes

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UF259

ANOTHER UPS

 

Inverter output voltage bus

CALL SERVICE

[2]

Minor

Flicker

ABNORMAL

 

abnormality

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF301

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF302

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF303

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF305

UPS CONTROL CIRCUIT

Control clock abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF306

UPS CONTROL CIRCUIT

Control power source circuit

CALL SERVICE

[1]

Major

Lit on

ERROR

 

abnormality

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF309

INVERTER VOLTAGE

Inverter output voltage abnormality

CALL SERVICE

[1]

Major

Lit on

ABNORMAL

 

before inverter power supply

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

UF310

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF349

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[1]

Major

Lit on

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF371

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[2]

Minor

Flicker

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF372

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[2]

Minor

Flicker

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF373

UPS CONTROL CIRCUIT

Control microcomputer abnormality

CALL SERVICE

[2]

Minor

Flicker

ERROR

 

ENGINEER

 

 

 

 

 

 

 

 

 

 

 

 

 

UF453

52L OPERATION ERROR

52L operated abnormally

CHECK 52L

[2]

Minor

Flicker

 

 

 

 

 

 

 

 

 

AC INPUT VOLTAGE OUT

AC input voltage deviates from +17%

CHECK INPUT

 

 

 

UA801

POWER

[2]

Alarm

-

OF RANGE

 

to –32% range

 

 

SOURCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT PHASE

 

 

CHECK INPUT

 

 

 

UA803

 

Input phase abnormal

POWER

[2]

Alarm

-

ROTATION ERROR

 

 

 

 

SOURCE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 50
Image 50
Mitsubishi 2033D SERIES technical manual INV. or Conv