MITSUBISHI

 

2033D SERIES UPS

Page Number:

 

ELECTRIC

OWNERS / TECHNICAL MANUAL

6-4

 

 

 

 

 

 

 

 

 

 

(Note 9)

 

 

 

 

(Note 1)

(Note 2)

(Note 3)

Code

Status message

 

Contents

Guidance

Buzzer

External

Failure

indication

 

 

 

 

 

send-out

lamp

 

 

 

 

 

 

contact

 

 

INVERTER OVERLOAD

 

WARNING:

 

 

 

UA806

Overload exceeded 105% (Note 7)

DECREASE

[2]

Alarm

-

> 100%

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INVERTER OVERLOAD

 

WARNING:

 

 

 

UA809

Overload exceeded 150% (Note 7)

DECREASE

[2]

Alarm

-

> 150%

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instantaneous overload. (Output

WARNING:

 

 

 

UA810

INVERTER OVERLOAD

DECREASE

[2]

Alarm

-

voltage -30% for 2ms)

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA812

BYPASS VOLTAGE OUT

Bypass voltage fell out of +/- 12%

CHECK BYPASS

[3]

Alarm

-

OF RANGE

 

range

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

UA813

BYPASS PHASE

 

Phase rotation is inverted when bypass

CHECK BYPASS

[2]

Alarm

-

ROTATION ERROR

 

voltage is normal

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

UA814

BYPASS FREQUENCY

Bypass frequency fell out of inverter

CHECK BYPASS

[3]

Alarm

-

OUT OF RANGE

 

synchronization follow-up range

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

UA817

EMERGENCY STOP

 

Emergency stop applied

-

-

Alarm

-

ACTIVATED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA832

ASYNCHRONOUS

 

Asynchronous transfer occurred

-

[2]

Alarm

-

TRANSFER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UA834

BATTERY DEPLETED

DC voltage dropped below discharge

-

-

Alarm

-

AC OUT STOPPED

 

end during inverter operation

 

 

 

 

 

 

 

 

 

 

 

 

 

UA835

BATTERY DEPLETED

Restart after battery depleted

-

-

Alarm

-

AND RESTART

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total of more than 110% load during

WARNING:

 

 

 

UA852

INVERTER OVERLOAD

DECEASE

[2]

Alarm

-

MMS operation.

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETRY START

 

Continuous bypass voltage abnormal,

 

 

 

 

UA853

 

inverter stop, and 72B closed for 1 min.

 

[2]

Alarm

-

OPERATION

 

 

 

 

will stop the UPS. (Fan stop)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 51
Image 51
Mitsubishi 2033D SERIES technical manual Inverter Overload