2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-2

WARNING 2

This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:

Capacity (kVA)

Bypass Voltage (Vac)

Bypass Rating (Aac)

Recommended

 

 

 

Breaker (Aac)

30

480

36

45

50

480

60

80

80

480

96

125

AC input and AC output over current protection and disconnect devices shall be field supplied and installed. DC output over current protection and disconnect device shall be field supplied and installed. The over current protection device shall be rated as indicated in TABLE 1.4.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 8
Image 8
Mitsubishi 2033D SERIES technical manual Capacity kVA