MITSUBISHI

 

 

 

 

2033D SERIES UPS

 

 

 

Page Number:

 

ELECTRIC

 

 

 

OWNERS / TECHNICAL MANUAL

 

 

 

3-5

 

 

TABLE 3.5 Recommended cable size and torque requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kVA

 

Input

 

Output

Input Side

* 1, 2

 

Output Side

* 1, 2

Bypass Side

* 1, 2

DC Input Side

* 1, 2

Capacity

 

Voltage

 

Voltage

Cable

 

Torque

 

Cable

 

Torque

Cable

 

Torque

Cable

 

Torque

 

 

 

 

 

Size

 

in. lbs

 

Size

 

in. lbs

Size

 

in. lbs

Size

 

in. lbs

30kVA

 

480V

 

480V

6 AWG

 

42-56

 

6 AWG

 

42-56

6 AWG

 

42-56

4 AWG

 

100-135

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

 

 

480V

 

208V

6 AWG

 

42-56

 

1 AWG

 

200-269

6 AWG

 

42-56

4 AWG

 

100-135

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

50kVA

 

480V

 

480V

3 AWG

 

200 - 269

 

4 AWG

 

100-135

3 AWG

 

200 - 269

1 AWG

 

200-269

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

 

 

480V

 

208V

3 AWG

 

200 - 269

 

3/0 AWG

 

347-469

3 AWG

 

200 - 269

1 AWG

 

200-269

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

80kVA

 

480V

 

480V

1/0 AWG

 

200-269

 

1/0 AWG

 

200-269

1/0 AWG

 

200-269

4/0 AWG

 

347-469

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

 

 

480V

 

208V

1/0 AWG

 

200-269

 

2x2/0 AWG

 

347 - 469

1/0 AWG

 

200-269

4/0 AWG

 

347-469

 

 

 

 

 

or larger

 

in. lbs

 

or larger

 

in. lbs

or larger

 

in. lbs

or larger

 

in. lbs

*1 – The cables must be selected to be equal to or larger than the sizes listed in the table. *2 - Voltage drop across power cables not to exceed 2% of nominal source voltage -

*3 - Allowable ampere rating based on 75 C insulation at ambient temperature of 40 C No more than 3 conductors in a raceway without de-rating.

Note : Copper conductors are assumed.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 37
Image 37
Mitsubishi 2033D SERIES technical manual Recommended cable size and torque requirements