MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-11

1.4Specifications

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The name plate is located on the inside of the UPS front door.

TABLE 1.1 Power Specifications

 

Rated output

Input voltage

Bypass input voltage

Output voltage

 

 

 

Power

3 phase / 3 wire

3 phase / 3 wire

3 phase / 3 or 4 wire

 

 

30kVA / 24kW

480V

 

 

480V

208V or 480V

 

 

50kVA / 40kW

480V

 

 

480V

208V or 480V

 

 

80kVA / 64kW

480V

 

 

480V

208V or 480V

 

 

TABLE 1.2 UPS Module Information

 

 

 

 

 

 

 

 

UPS

CABLE

 

WIDTH

DEPTH

HEIGHT

 

WEIGHT

HEATING

 

 

[kVA]

ENTRY

 

[in / mm]

[in / mm]

[in / mm]

 

[lb./ kg]

[kBTU/h]

 

 

 

 

 

 

 

 

 

 

 

 

30

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

2060 / 930

9.1

 

 

50

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

1810 / 820

13.5

 

 

80

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

1990 / 900

21.6

 

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 17
Image 17
Mitsubishi 2033D SERIES technical manual Specifications