OWNERS / TECHNICAL MANUAL

1-7

C) Inverter supply at battery operation

FIGURE 1.3 Single Line Diagram - Battery Operation

CB

AC Bypass

Input

CB

AC input

User supplied

 

 

Static Transfer

 

Maintenance

 

 

 

Bypass

 

 

Switch

 

 

 

 

Switch

 

52RS

 

 

 

 

 

 

 

CONVERTER

INVERTER

 

 

 

 

 

 

Output

52RC

FI

FO

52C

52CS

 

 

 

 

 

 

FB

 

 

 

 

72B

 

Power Flow

 

 

 

 

 

BATTERY

 

 

Not in Use

 

50kVA,

80kVA:

 

 

 

UPS Module

 

 

External Battery

Referring to Figure 1.3: In the event of AC input source failure or interruption, the converter will de-energize and the battery will immediately discharge and supply DC power to the inverter to maintain continuous AC power to the load. This operation will continue until:

a)The battery capacity expires and the inverter turns off, or

b)Input power is restored after which the converter will power the inverter and critical load and simultaneously recharge the batteries.

A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.

When power is restored after a low battery shutdown, the converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention.

The power drawn by the load is equally shared between all system UPS during battery operation.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 13