iv.One (1) source feeding the UPS:
(1)Confirm that an external input circuit breaker sized to protect both the converter input and the bypass line is installed. (Refer to equipment nameplate for current ratings.) Connect the bypass input power cables from the input service entrance to the bypass input power terminals, identified as A40, B40, and C40 in Figures
(2)Using adequately sized conductors per Table 3.5 and referring to the appropriate figure identified in Figures
(3)Referring to Figures
(4)Connect the external signal terminal block as desired. Refer to section 2.5 and Figure 2.15 for functional description. 12 AWG, or less, shielded conductor is recommended.
NOTES: 1. Confirm that all UPS internal contactors (breakers) "52RC "72B",”52RS”, and "52C" are open before energizing UPS.
2.UPS power terminals are supplied with stud type fittings. It is recommended that compression lugs be used to fasten all input/output power cables. Refer to Table 3.6 for recommended compression lugs and appropriate crimping tool.