MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

2-10

A)Output Contacts (for external alarm annunciation)

Output contacts consist of form Adry type contacts. Rated capacity of all output contacts is NEC Class2 (30Vdc/1Adc). All dry contacts should be operated at their rated values or lower. Figure 2.16 illustrates a typical installation. The external relay can also be a lamp, LED, computer, etc.

FIGURE 2.16 Control Wiring for External Contacts

UPS Cabinet

Terminal

Relay

ContactTerminal

External to UPS Cabinet

Relay

Coil

NEC Class 2 Power Source

User supplied

Details of output alarm contacts : TN1

Terminals 1 to 2, 3 to 4 "UPS failure" contact

Activated when a major fault has occurred to the system. Terminals 5 to 6, 7 to 8 "Load on Bypass" contact (OUT1)

Activated when the power is supplied from the static bypass input. Terminals 9 to 10, 11 to 12 "Load on Inverter" contact (OUT2)

Activated when the power is supplied by the inverter. Terminals 13 to 14, 15 to 16 "Battery Operation" contact (OUT3)

Activated when the battery is operating following an AC power failure. Terminals 17 to 18, 19 to 20 "Converter Operation" contact (OUT4)

Activated when the converter is operating.

Terminals 21 to 22, 23 to 24 "Battery Low Voltage" contact (OUT5)

Activated when the battery voltage drops below discharge end voltage level during inverter operation (i.e. During AC fail condition).

Terminals 25 to 26, 27 to 28 "Overload" contact (OUT6) Activated when an overload has occurred to the system.

Terminals 29 to 30, 31 to 32 "Bypass Sync.” contact (OUT7) Activated when the system is in sync. Mode.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 29
Image 29
Mitsubishi 2033D SERIES Output Contacts for external alarm annunciation, Control Wiring for External Contacts