MITSUBISHI

2033D SERIES UPS

ELECTRIC

OWNERS / TECHNICAL MANUAL

2.) Battery log (FIGURE 2.10)

This screen displays the cumulative battery discharging record.

FIGURE 2.10 Battery log screen

Page Number:

2-6

36A

2.4.2 INPUT POWER FAILURE

During an Input Power Failure, the UPS inverter will be powered by the UPS batteries. The following will be displayed on the main and measurement screen (Indication of battery remaining capacity).

FIGURE 2.11 Main screen

FIGURE 2.12 Measurement screen

(Battery operation)

(Battery operation)

480V

48A

STS

52RC52C

72B

480V48A

32kW

48A

48A

48A

The LCD will display a battery low voltage message when the battery capacity is near depletion. The End of Battery Discharge announcement is displayed when the battery end voltage is reached. At this time, the inverter will perform an electronic shutdown to prevent battery loss of life typical from extreme deep discharge conditions. When the input power is restored, the inverter will automatically restart to power the load, and the batteries will be simultaneously recharged. The End of Battery announcement is shown at the bottom of the screen.

MITSUBISHI ELECTRIC 2033D SERIES UPS

Page 25
Image 25
Mitsubishi 2033D SERIES technical manual Input Power Failure, Main screen