3.0INSTALLATION AND OPERATION

3.1Transportation and Installation

TABLE 3.1 How to transport and install the system

Transportation

Installation

Transport unit with forklift.

Using the pre drilled holes (4 - 24) in the

Carry with overhead crane using

UPS channel base, anchor the unit using

eyebolts provided.

appropriate hardware. (Not provided)

Note : Do not transport in a horizontal position. Cabinets must be maintained upright within +/- 15° of the vertical during handling.

3.2Installation Procedure

A)Note the load tolerance of the floor Refer to Table 3.2 for list of UPS weights.

TABLE 3.2 List of UPS weights

UPS Capacity (kVA)

30

50

80

Weight (lb)

2060

1810

1990

B)Minimum clearance required for ventilation

Right side

1.0" (25 mm) (not required when sidecars are used)

Left side

1.0"

(25 mm) (not required when sidecars are used)

Back side

0.0"

(0.0 mm)

Top side

23.6" (600 mm) (for air flow)

C)Space requirement for routine maintenance

Allow for the following space at the time of installation.

Front

39.4" (1000 mm)

Sides

0.0" (0.0 mm)

Rear

0.0" (0.0 mm)