OUTDOOR INSTALLATION

P/N 471048

OUTDOOR INSTALLATION

POWERMAX VENTING GUIDELINES

G

Outdoor

Stack Kit

F

6 in. min.

 

A

D

1'

3'

C

4'

4'

B

4'

Property Line

E

A-6

Walkway

F Optional Horizontal Venting.

ECheck local building codes for setback requirements.

The Vent Pipe:

Must be the same diameter as the vent connector.

Must be suitable for use with Category III Appliances which have flue gas temperatures of less than 400 deg. F.

Vent Termination:

Must be not less than 7 ft. above public walkways.

AMust be at least 3 ft. above any forced air inlet located within a 10 ft. radius.

Must be located the following distances away from any door, window, or gravity air inlet:

B4 ft. below, or

C4 ft. horizontally, or

D1 ft. above

G

POWERMAX OUTDOOR STACK KITS

MODEL

STACK DIA.

KIT MODEL

 

PMX 150

3"

471395

 

PMX 200

3"

471395

 

PMX 250

4"

471396

 

PMX 300

4"

471396

 

PMX 350

4"

471396

 

PMX 400

4"

471396

Rev. G 1-22-04

(DIAGRAM 2)

Page 32
Image 32
Pentair PowerMax Outdoor Installation Powermax Venting Guidelines, The Vent Pipe, Vent Termination, Diagram