Pentair MiniMax Plus HP Series, PowerMax installation manual Stack Type Indoor Draft Hood Kit

Models: MiniMax Plus HP Series PowerMax

1 40
Download 40 pages 37.76 Kb
Page 19
Image 19
Air supply requirements below apply to all

Installation (contd.)

19

 

 

 

 

NOTE

The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen for proper gas combustion. The air supply openings should be sized according to Tables 10. and 11.

Air supply requirements below apply to all

b)Construct a non-combustible base from masonry blocks as illustrated, see Figure 23.

MiniMax heaters, including PowerMax versions.

 

All Air From Inside

 

 

 

Model

Air for Combustion

Air Ventilation

Sq. In.

Sq. In.

 

 

 

 

150

150

150

 

 

 

195/200

200

200

 

 

 

250

250

250

 

 

 

300

300

300

 

 

 

350

350

350

 

 

 

400

400

400

BASE FOR USE ON COMBUSTIBLE FLOORS

SHEET METAL

BLOCKS

T

O

H

. MiniMax heaters, including PowerMax versions. Min 6" STACK TYPE INDOOR DRAFT HOOD KIT

. Manual background Min 6"

Manual background HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH

24 GA. (MIN.) GALVANIZED SHEET METAL.

Table 10.

Figure 23.

 

All Air From Outside

 

 

 

Model

Air for Combustion

Air Ventilation

Sq. In.

Sq. In.

 

 

 

 

150

37

37

 

 

 

195/200

50

50

 

 

 

250

63

63

 

 

 

300

77

77

 

 

 

350

90

90

 

 

 

400

100

100

 

 

 

Manual backgroundCAUTION

Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.

Table 11.

INSTALLATION ON FLOORS CONSTRUCTED OF COMBUSTIBLE MATERIALS

The heater may be placed on a “combustible floor” using either of the two methods listed below:

a)Use Listed Factory Non-combustible Base Kit for use on combustible floors.

Model

Non-Combustible Base Kit

 

 

150

471389

 

 

195/200

471390

 

 

250

471391

 

 

300

471392

 

 

350

471393

 

 

400

471394

 

 

Table 12.

Rev. G 1-22-04

STACK TYPE INDOOR DRAFT HOOD KIT

The proper draft hood and adapter must be installed on the heater as shown below and on page 20:

Model

Draft Hood

Product No.

Vent Dia.

 

 

 

 

150

DH15

460227

6 in.

 

 

 

 

195/200

DH20

460228

7 in.

 

 

 

 

250

DH25

460230

7 in.

 

 

 

 

300

DH30

460231

8 in.

 

 

 

 

350

DH35

460233

9 in.

 

 

 

 

400

DH40

460234

10 in.

 

 

 

 

Table 13.

P/N 471048

Page 19
Image 19
Pentair MiniMax Plus HP Series, PowerMax Stack Type Indoor Draft Hood Kit, Air supply requirements below apply to all