Installation (contd.) | 16 |
GAS CONNECTIONS
Pipe Sized For Length Of Run In Equivalent Feet Table 7.
|
| 1/2 in. |
| 3/4 in. | 1 in. | 1¼ in. | 1½in. | 2 in. | |||||||
GAS LINE INSTALLATIONS | Model | Nat | LP | Nat | LP | Nat | LP | Nat | LP | Nat | LP | Nat | LP | ||
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Before installing the gas line, be sure to | 150 | 10' | 40' | 50' | 150' | 150' | 600' | - | - | - | - | - | - | ||
check which gas the heater has been | |||||||||||||||
195/200 | - | 20' | 30' | 80' | 125' | 250' | 450' | 600' | - | - | - | - | |||
designed to burn. This is important | |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
because different types of gas require | 250 | - | 10' | 20' | 50' | 70' | 150' | 250' | 500' | 600' | - | - | - | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
different gas pipe sizes. The rating plate | 300 | - | - |
| 10' | 30' | 50' | 100' | 200' | 350' | 400' | 600' | - | - | |
|
|
| |||||||||||||
on the heater will indicate which gas the | 350 | - | - |
| 10' | 20' | 30' | 70' | 125' | 250' | 250' | 500' | 500' | - | |
heater is designed to burn. Table 7, | 400 | - | - |
| - | 10' | 20' | 60' | 100' | 150' | 200' | 450' | 400' | - | |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
shows which size pipe is required for the |
|
| REGULATED MANIFOLD PRESSURE TEST |
| |||||||||||
distance from the gas meter to the heater. The table |
|
| |||||||||||||
| 1. Attach the manometer to the heater jacket. |
|
| ||||||||||||
is for natural gas at a specific gravity of .65 and |
|
|
| ||||||||||||
propane at specific gravity of 1.5. |
|
| 2. | Shut off the main gas valve. |
|
|
|
|
| ||||||
|
| 3. | Remove 1/8 in. NPT plug on the outlet side of the |
| |||||||||||
|
|
|
| ||||||||||||
When sizing gas lines, calculate three (3) additional |
|
| valve and screw in the fitting from the manometer kit. | ||||||||||||
feet of straight pipe for every elbow used. |
|
| 4. Connect the manometer hose to the fitting. |
|
| ||||||||||
When installing the gas line, avoid getting dirt, |
| 5. | Fire the heater. |
|
|
|
|
|
|
| |||||
| 6. | The manometer must read 4 in. WC for natural gas, | |||||||||||||
grease or other foreign material in the pipe as this |
|
| 11 in. WC for propane gas, while the heater is |
| |||||||||||
may cause damage to the gas valve, which may |
|
| operating. |
|
|
|
|
|
|
|
| ||||
result in heater failure. |
|
| 7. | For adjustment, remove the Regulator Adjustment | |||||||||||
The gas meter should be checked to make sure that |
|
| Cap and using a screwdriver turn the screw clock- | ||||||||||||
|
| wise to increase - counterclockwise to decrease gas | |||||||||||||
it will supply enough gas to the heater and any other |
|
| pressure. |
|
| Regulator Adjustment Cap |
|
|
| ||||||
appliances that may be used on the same meter. |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
| 1/8" NPT Plug |
|
|
|
|
|
| ||||
|
|
|
|
|
|
| (Inlet Press) |
|
|
|
|
|
| ||
The gas line from the meter will usually be of a |
|
| Figure 16. |
|
|
|
|
|
|
|
| ||||
larger size than the gas valve supplied with the |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| ON |
|
|
| |||
heater. Therefore a reduction of the connecting gas |
|
|
|
|
|
|
|
| OFF |
|
|
|
| ||
pipe will be necessary. Make this reduction as close |
|
|
|
|
|
|
| 1/8" NPT Plug |
|
|
|
|
| ||
to the heater as possible. |
|
|
|
|
|
|
|
| (Manifold Press) |
|
|
|
| ||
|
|
|
|
|
|
|
| ADJUSTMENT CAP |
|
|
| ||||
|
|
|
|
|
|
|
|
| REGULATOR |
|
|
| |||
The heater and any other gas appliances must be |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
disconnected from the gas supply piping system |
|
| Figure 17. |
|
|
|
|
|
|
|
| ||||
during any pressure testing on that system, (greater |
|
|
|
|
|
| PILOT |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
that ½ PSIG). |
|
|
|
|
|
|
|
| HONEYWELL |
|
|
|
|
| |
|
|
|
|
|
|
|
| 1/2 P.S.I. |
| PRESS |
|
| |||
|
|
|
|
|
|
|
|
| PILOT |
| TAP |
|
|
| |
|
|
|
|
|
|
|
|
| ADJ. |
|
|
|
|
| |
The heater and its gas connection must be leak |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
tested before placing the heater in operation. Do not |
|
|
|
|
|
| CAUTION |
|
|
| |||||
use flame to test the gas line. Use soapy water or |
| The use of Flexible Connectors (FLEX) is NOT |
|
| |||||||||||
another nonflammable method. |
|
|
|
| |||||||||||
|
| recommended as they cause high gas pressure drops. | |||||||||||||
|
|
| |||||||||||||
A manual main |
| MINIMAX PLUS GAS PRESSURE REQUIREMENTS* | |||||||||||||
externally to the heater. |
|
|
WARNING
Do not install the gas line union inside the heater cabinet. This will void your warranty.
P/N 471048
| Natural | Propane |
|
|
|
Maximum inlet gas pressure | 10 in. WC | 14 in. WC |
Minimum inlet gas pressure | **5 in. WC | 12 in. WC |
Normal manifold pressure | 4 in. WC | 11 in. WC |
** 6 WC for 400 model |
|
|
*All Readings are taken with the heater fired. Any adjustments | ||
made with heater off will give incorrect readings. |
| |
Table 8. |
|
|
| Rev. G |