A sensitive static-pressure controller directly compares the variations between the space static pressure and the outdoor reference static pressure. The controller modulates the capacity of a central relief fan to maintain a fixed static-pressure difference, usually a slightly positive building pressure. The space static-pressure sensor is typically located in the lobby or near the main entrance.

period five

Application Considerations

notes

A sensitive static-pressure controller directly compares the variations between the space static pressure and the outdoor reference static pressure. The controller modulates the capacity of a central relief fan to maintain a fixed static-pressure difference, usually a slightly positive building pressure. The space static-pressure sensor is typically located in the lobby or near the main entrance.