Trane TRG-TRC014-EN manual Fan Control Loop, VAV Fan Modulation, period four

Models: TRG-TRC014-EN

1 93
Download 93 pages 18.85 Kb
Page 62
Image 62
Fan Control Loop

period four

Fan Modulation

notes

Fan Control Loop

static-pressure

supplysensor fan

controller

Figure 78

To achieve this balance, a simple control loop is used. First, the static pressure is sensed from a particular location in the system. Second, a controller compares this static pressure reading and the set point of the system. Finally, the fan capacity is controlled to deliver the required airflow, at a static pressure that maintains this set point at the location of the system sensor.

VAV Fan Modulation

static pressure

sensor VAV Fan Modulation set point

actual system resistance curve

design system resistance curve

Manual background A

VAV system

 

modulation curve

B

 

airflow

Figure 79

 

We will use an exaggerated example to illustrate this system operation. Assume that the load on the system decreases, causing all or part of the VAV terminal units to modulate closed. This causes the system resistance curve to shift upwards.

In response, the fan begins to “ride up” the constant-speed performance curve from the design operating point (A), trying to reach the balance point with this new system resistance curve. As a result, the fan delivers a lower airflow at a higher static pressure.

TRG-TRC014-EN

57

Page 62
Image 62
Trane TRG-TRC014-EN manual Fan Control Loop, VAV Fan Modulation, period four