Trane UD1B080A9H31B, UD1D120A9H51B, UD1B060A9H31B, UD1C080A9H41B, UD1B100A9H31B Installer’s Guide

Models: DD1C100A9H51B DD1D120A9H51B DD1B080A9H31B DD1B060A9H31B UD1C100A9H51B UD1D140A9H51B UD1A040A9H21B UD1B080A9H31B UD1B100A9H31B UD1C080A9H41B UD1B060A9H31B UD1D120A9H51B

1 24
Download 24 pages 20.54 Kb
Page 16
Image 16
Manual background

Installer’s Guide

TABLE 8

GAS VENT TERMINATION

ROOF PITCH

MINIMUM HEIGHT

 

 

FLAT TO 7/12

1.0 FEET *

OVER 7/12 TO 8/12

1.5 FEET

OVER 8/12 TO 9/12

2.0 FEET

OVER 9/12 TO 10/12

2.5 FEET

OVER 10/12 TO 11/12

3.25 FEET

OVER 11/12 TO 12/12

4.0 FEET

OVER 12/12 TO 14/12

5.0 FEET

OVER 14/12 TO 16/12

6.0 FEET

OVER 16/12 TO 18/12

7.0 FEET

OVER 18/12 TO 20/12

7.5 FEET

OVER 20/12 TO 22/12

8.0 FEET

* THIS REQUIREMENT COVERS MOST INSTALLATIONS

d

8.Where long periods of airflow are desired for com- fort, use long fan cycles instead of continuous air- flow.

9.Apply other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223.1 “latest edition”.

10.Vent connectors serving appliance vented by natural draft or non-positive pressure shall not be connected into any portion of a mecha- nized draft system operating under positive pressure.

11.Horizontal pipe runs must be supported by hangers, straps or other suitable material in intervals at a minimum of every 3 feet of pipe.

12.A furnace shall not be connected to a chimney or flue serving a separate appliance designed to burn solid fuel.

13.The flow area of the largest section of vertical vent or chimney shall not exceed 7 times the smallest listed appliance categorized vent area, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods.

Maximum Vent or Tile

=

π(D*)2

X 7

Lined Chimney Flow Area

4

 

 

 

 

*Drafthood outlet diameter, flue collar diameter, or listed appliance cat- egorized vent diameter.

ELECTRICAL CONNECTIONS

! WARNING

The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/ NFPA 70 – “latest edition” and Canadian Electrical Code, CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur.

Failure to follow this warning could result in an electri- cal shock, fire, injury, or death.

! CAUTION

The integrated furnace control is polarity sensitive. The hot leg of the 115 VAC power must be connected to the BLACK field lead.

! WARNING

To prevent injury or death due to electrical shock or contact with moving parts, lock unit disconnect switch in the open position before servicing the unit.

Failure to follow this warning could result in electri- cal shock, personal injury, or death.

Make wiring connections to the unit as indicated on en- closed wiring diagram. As with all gas appliances using electrical power, this furnace shall be connected into a permanently live electric circuit. It is recommended that it be provided with a separate “circuit protection device” electric circuit. The furnace must be electrically grounded in accordance with local codes or in the ab- sence of local codes with the National Electrical Code, ANSI/NFPA 70 “latest edition” or Canadian Electrical Code, CSA C22.1, if an external electrical source is uti- lized.

All field supplied wiring must conform with the tem- perature limitation for Type T wire [63° F. (35° C)], when installed in accordance with these instructions and wiring diagrams supplied with the furnace. A dis- connecting means must be located within sight from, and readily accessible to, the furnace.

Refer to the SERVICE FACTS literature for unit wiring diagrams in addition to the diagram inside the blower door.

16

18-CD21D1-5

Page 16
Image 16
Trane UD1B080A9H31B, UD1D120A9H51B, UD1B060A9H31B, UD1C080A9H41B, UD1B100A9H31B, UD1A040A9H21B, UD1D140A9H51B Installer’s Guide