▲! WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could re- sult in serious injury, death or property damage. Never test for gas leaks with an open flame. Use a commer- cially available soap solution made specifically for the detection of leaks to check all connections. A fire or ex- plosion may result causing property damage, personal injury, or loss of life.
fLEFT SIDE PIPING (STANDARD)
RIGHT SIDE PIPING (OPTIONAL)
TOP VIEW OF RIGHT SIDE PIPING
▲! WARNING
TO PREVENT AN EXPLOSION OR POSSIBLE INJURY, DEATH AND EQUIPMENT DAMAGE, DO NOT STORE COMBUSTIBLE MATERIALS, GASOLINE OR OTHER FLAMMABLE VAPORS OR LIQUIDS NEAR THE UNIT.
Installer’s Guide
GAS PIPING
This unit is shipped standard for left side installation of gas piping. A piping knockout is also provided in the right side for an alternate piping arrangement. The in- stallation of piping shall be in accordance with piping codes and the regulations of the local gas company. Pipe joint compound must be resistant to the chemical reac- tion with liquefied petroleum gases.
Refer to piping Table 9 for delivery sizes. Connect gas supply to the unit, using a ground joint union and a manual
The furnace and its individual
The furnace must be isolated from the gas supply piping by closing its individual manual
▲! CAUTION
Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold assembly.
NOTE:
Maximum pressure to the gas valve for natural gas is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum pressure to the gas valve for propane is 13.8" W.C. Minimum pressure is 11.0" W.C.
All gas fittings must be checked for leaks using a soapy solution before lighting the furnace.
DO NOT CHECK WITH AN OPEN FLAME!
The following warning complies with State of California law, Proposition 65.
▲! WARNING
Hazardous Gases!
Exposure to fuel substances or
SEQUENCE OF OPERATION
THERMOSTAT CALL FOR HEAT
R and W thermostat contacts close signaling the control module to run its