Selection Procedure
Model S
Maximum mounting heights for Model S Unit Heaters are given inTable
Mounting the unit at or below maximum mounting height will insure that heated air reaches the living zone.
Model P
Maximum mounting heights for Model P Unit Heaters are given inTable
Where ceilings are unusually low, a nearly horizontal flow of air can be obtained by equipping these units with Louver Cone Diffusers.The individually adjustable blades of the Louver Cone permit an infinite variety of adjustments to meet any
Table
Table Based on 2 PSIG and 60 F Entering Air
Steam |
|
|
|
|
| Temperature of Entering Air (F) |
|
|
|
|
| ||
Pressure PSIG | 0 | 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | ||
| 0 | 1.54 | 1.45 | 1.37 | 1.27 | 1.19 | 1.11 | 1.03 | 0.96 | 0.88 | 0.81 | 0.74 | 0.67 |
| 2 | 1.59 | 1.50 | 1.41 | 1.32 | 1.24 | 1.16 | 1.08 | 1.00 | 0.93 | 0.85 | 0.78 | 0.71 |
| 5 | 1.64 | 1.55 | 1.46 | 1.37 | 1.29 | 1.21 | 1.13 | 1.05 | 0.97 | 0.90 | 0.83 | 0.76 |
Blow- | 10 | 1.73 | 1.64 | 1.55 | 1.46 | 1.38 | 1.29 | 1.21 | 1.13 | 1.06 | 0.98 | 0.91 | 0.84 |
Through | 15 | 1.80 | 1.71 | 1.61 | 1.53 | 1.44 | 1.34 | 1.28 | 1.19 | 1.12 | 1.04 | 0.97 | 0.90 |
Type | 20 | 1.86 | 1.77 | 1.68 | 1.58 | 1.50 | 1.42 | 1.33 | 1.25 | 1.17 | 1.10 | 1.02 | 0.95 |
| 30 | 1.97 | 1.87 | 1.78 | 1.68 | 1.60 | 1.51 | 1.43 | 1.35 | 1.27 | 1.19 | 1.12 | 1.04 |
| 40 | 2.06 | 1.96 | 1.86 | 1.77 | 1.68 | 1.60 | 1.51 | 1.43 | 1.35 | 1.27 | 1.19 | 1.12 |
| 50 | 2.13 | 2.04 | 1.94 | 1.85 | 1.76 | 1.67 | 1.58 | 1.50 | 1.42 | 1.34 | 1.26 | 1.19 |
| 60 | 2.20 | 2.09 | 2.00 | 1.90 | 1.81 | 1.73 | 1.64 | 1.56 | 1.47 | 1.39 | 1.31 | 1.24 |
| 70 | 2.26 | 2.16 | 2.06 | 1.96 | 1.87 | 1.78 | 1.70 | 1.61 | 1.53 | 1.45 | 1.37 | 1.29 |
| 75 | 2.28 | 2.18 | 2.09 | 1 .99 | 1.90 | 1.81 | 1.72 | 1.64 | 1.55 | 1.47 | 1.40 | 1.32 |
Notes:
To determine the Btu per hour capacity of a Model S Horizontal Unit Heater at any steam pressure and entering air temperature multiply rated capacity at 2 psig steam 60 F entering air (Table