Power

Table EP-1 Electric Power — Model S Unit Heater — Motor

 

 

Accessory

 

 

 

 

 

Model

Motor

Operating

 

 

MAX

 

 

Number

Type

Voltage

AMP

MCA

FUSE

HP

RPM

18,19,20

Totally Enclosed

115/60/1

0.35

0.4

15

1/50*

1075

31,38,42,45,60

Totally Enclosed

115/60/1

2.1

2.6

15

1/20*

1550

53,69,70,77,90,100

Totally Enclosed

115/60/1

1.7**

2.1

15

1/8*

1550

91,126,127,168

Totally Enclosed

115/60/1

2.3**

2.9

15

1/6

1100

137,181,186,230

Totally Enclosed

115/60/1

3.6**

4.5

15

1/4

1100

207,243,260,273,320,354

Totally Enclosed

115/60/1

5.4**

6.8

15

1/2

1100

18,19,20

Totally Enclosed

208-230/460/60/3

0.98-1.1/0.55

1.2-1.4/0.7

15-15/15

1/6

1140

31,38,42,45,60

Totally Enclosed

208-230/460/60/3

0.98-1.1/0.55

1.2-1.4/0.7

15-15/15

1/6

1140

53,69,70,77,90,100

Totally Enclosed

208-230/460/60/3

0.98-1.1/0.55

1.2-1.4/0.7

15-15/15

1/6

1140

91,126,127,168

Totally Enclosed

208-230/460/60/3

0.98-1.1/0.55

1.2-1.4/0.7

15-15/15

1/6

1140

137,181,186,230

Totally Enclosed

208-230/460/60/3

1.2-1.4/0.7

1.5-1.8/0.9

15-15/15

1/4

1140

207,243,260,273,320,354

Totally Enclosed

208-230/460/60/3

1.8-2.0/1.0

2.3-2.5/1.3

15-15/15

1/2

1140

400

Totally Enclosed

208-230/460/60/3

3.1-3.2/1.6

3.9-4.0/2.0

15-15/15

3/4

1140

*Optional variable speed switch is available.

**These motors have automatic thermal overload protection or impedance protection.

Table EP-2 Electric Power — Model S Unit Heater — Motor

 

 

Accessory

 

 

 

 

 

Model

Motor

Operating

 

 

MAX

 

 

Number

Type

Voltage

AMP

MCA

FUSE

HP

RPM

 

Explosion Proof

 

 

 

 

 

 

18,19,20

with Thermal Overload

115/60/1

3.8

4.8

15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

31,38,42,45,60

with Thermal Overload

115/60/1

3.8

4.8

15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

53,69,70,77,90,100

with Thermal Overload

115/60/1

3.8

4.8

15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

91,126,127,168

with Thermal Overload

115/60/1

3.8

4.8

15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

137,181,186,230

with Thermal Overload

115/60/1

4.4

5.5

15

1/4

1140

 

Explosion Proof

 

 

 

 

 

 

207,243,260,273,320,354

with Thermal Overload

115/60/1

7.8

9.8

15

1/2

1140

 

Explosion Proof

 

 

 

 

 

 

18,19,20

with Thermal Overload

208-230/460/60/3

1.0-1.0/0.5

1.3-1.3/0.6

15-15/15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

31,38,42,45,60

with Thermal Overload

208-230/460/60/3

1.0-1.0/0.5

1.3-1.3/0.6

15-15/15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

53,69,70,77,90,100

with Thermal Overload

208-230/460/60/3

1.0-1.0/0.5

1.3-1.3/0.6

15-15/15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

91,126,127,168

with Thermal Overload

208-230/460/60/3

1.0-1.0/0.5

1.3-1.3/0.6

15-15/15

1/6

1140

 

Explosion Proof

 

 

 

 

 

 

137,181,186,230

with Thermal Overload

208-230/460/60/3

1.1-1.1/0.55

1.4-1.4/0.7

15-15/15

1/4

1140

 

Explosion Proof

 

 

 

 

 

 

207,243,260,273,320,354

with Thermal Overload

208-230/460/60/3

3.1-3.2/1.6

3.9-4.0/2.0

15-15/15

3/4

1145

 

Explosion Proof

 

 

 

 

 

 

400

with Thermal Overload

208-230/460/60/3

3.1-3.2/1.6

3.9-4.0/2.0

15-15/15

3/4

1145

Table EP-3Electric Power — Model S Unit Heater —Motor

 

 

Accessory

 

 

 

 

 

Model

Motor

Operating

 

 

MAX

 

 

Number

Type

Voltage

AMP

MCA

FUSE

HP

RPM

18-230

Totally Enclosed

575/60/3

0.6

0.8

15

1/3

1140

207,243,260,273,320,354

Totally Enclosed

575/60/3

0.8

1.0

15

1/2

1140

400

Totally Enclosed

575/60/3

1.3

1.6

15

3/4

1140

CAUTION: Select appropriate AMP, MCA, and MAX FUSE for the multiple voltage motors. For example, the AMP, MCA, and MAX FUSE for Model 18 with a 230 volt Totally Enclosed motor is 1.1, 1.4, and 15 respectively.