Selection

Procedure

Table SP-4 – Model S Horizontal Unit Heater Steam Capacities con’t

2 Lbs. Steam 60 F Entering AirTemp

 

Motor

Motor

BTU

 

Condensate

Final

CFM 70 F

Outlet

Oper.

Size

HP

RPM

Per Hour

EDR

Lbs Per Hr

Temp

Air Basis

Velocity

Weight

 

 

 

 

Low FinalTemp. “Bypass” Units

 

 

 

 

 

 

1050

19,300

80

20

106

390

220

 

 

19-S2

1/25

950

18,300

77

19

108

360

205

40

 

 

800

16,300

68

17

110

300

173

 

 

 

 

1550

30,400

127

31

104

635

359

 

 

31-S

1/20

1300

27,800

116

29

109

520

302

40

 

 

1100

25,300

106

26

112

450

257

 

 

 

 

1550

45,800

191

47

107

897

363

 

 

45-S

1/20

1300

41,300

173

43

112

740

304

55

 

 

1100

37,300

156

39

116

630

259

 

 

 

 

1550

53,300

223

55

105

1090

439

 

 

53-S

1/8

1300

50,200

209

52

109

940

383

55

 

 

1100

46,200

192

48

114

795

327

 

 

 

 

1550

69,400

290

72

108

1337

407

 

 

69-S

1/8

1300

63,400

264

66

112

1125

346

70

 

 

1100

57,600

240

60

116

955

295

 

 

 

 

1550

76,600

320

79

107

1510

458

 

 

77-S

1/8

1300

71,700

299

74

111

1304

300

80

 

 

1100

65,800

274

68

116

1100

341

 

 

91-S

1/6

1100

91,000

380

94

108

1740

394

95

127-S

1/6

1100

125,800

524

130

108

2440

448

135

137-S

1/4

1100

135,800

567

140

107

2700

495

135

181-S

1/4

1100

180,700

755

187

109

3392

430

180

207-S

1/2

1100

206,900

863

214

107

4059

514

185

243-S

1/2

1100

238,700

995

248

108

4607

439

230

273-S

1/2

1100

272,200

1135

283

105

5644

536

235

Notes:

1.Constant speed units are rated at capacities shown in regular type: Capacities in italic faced type apply only to units with multi-speed motors.

2.Capacities based on 2 psi steam and 60 F entering air.

16

UH-PRC001-EN

Page 16
Image 16