TRENDnet SMT1000 Customize the Main and Controlled Outlet Groups, WHEN ON BATTERY setting

Models: SMT1000

1 18
Download 18 pages 36.13 Kb
Page 13
Image 13

Customize the Main and Controlled Outlet Groups

Use the Configuration menus to change the Main Outlet Group and the Controlled Outlet Group settings.

Function

Factory Default

Options

Description

 

 

 

 

Name String

Outlet Group 1

Edit these names using an external interface, such as the Network

Outlet Group

 

 

 

Management Card Web interface.

UPS Name String

UPS Outlets

 

 

 

 

 

 

Turn On Delay

 

Set the value in

The amount of time the UPS or a Controlled Outlet

0 sec

Group will wait between receiving the command to

seconds

 

 

turn on and the actual startup.

 

 

 

 

 

 

 

Turn Off Delay

• 0 sec UPS Outlets

Set the value in

The amount of time the UPS or a Controlled Outlet

• 90 sec Controlled

Group will wait between receiving the command to

seconds

 

Outlet Groups

turn off and the actual shut down.

 

 

 

 

 

 

Reboot Duration

8 sec

Set the value in

The amount of time the UPS or a Controlled Outlet

seconds

Group must remain off before it will restart.

 

 

 

 

 

 

Minimum Return

 

Set the value in

The amount of battery runtime that must be available

0 sec

before the UPS or a Controlled Outlet Group will

Time

seconds

 

turn on after a shutdown.

 

 

 

 

 

 

 

 

 

• Enable

When the unit switches to battery power, the UPS

 

 

• Disable

will disconnect power to the Controlled Outlet

Load Shed On

 

 

Group to save battery runtime.

Disabled

 

 

Battery

 

Configure this delay time, use the LOAD SHED TIME

 

 

 

 

 

WHEN ON BATTERY setting.

 

 

 

 

Load Shed Time

1800 sec

Set the value in

The amount of time the outlets will function on

when On Battery

seconds

battery power before they will turn off.

 

 

 

 

 

 

 

• Enable

When the battery runtime falls below the specified

Load Shed On

Disabled

• Disable

value, the Controlled Outlet Group will turn off.

 

 

Runtime

 

Configure this time using the LOAD SHED RUNTIME

 

 

 

 

 

 

 

 

REMAINING setting.

 

 

 

 

Load Shed On

 

Set the value in

When the remaining runtime reaches this level, the

Runtime

120 sec

seconds

Controlled Outlet Group will turn off.

Remaining

 

 

 

 

 

 

 

 

 

 

• Disabled

In the event of an overload (greater than 107%

Load Shed on

Disabled

• Enabled

output), the Controlled Outlet Group will

 

immediately turn off to conserve power for critical

Overload

 

 

 

loads. The Controlled Outlet Group will only turn on

 

 

 

 

 

 

again with a manual command.

 

 

 

 

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set at the factory. These settings can only be modified using an external interface, such as the NMC Web interface.

NMC IP Address Mode

NMC IP Address

NMC Subnet Mask

NMC Default Gateway

Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower

11

Page 13
Image 13
TRENDnet SMT1000 Customize the Main and Controlled Outlet Groups, Network Management Card Settings, REMAINING setting