Configuration

UPS Settings

Start up Settings

Configure these settings at initial start up, using the display interface. As an alternative, configuration can be performed using PowerChutesoftware.

Note: During start up, use the display interface to configure these settings. If nothing is selected, the unit will use the default settings.

Function

Factory Default

Options

Description

 

 

 

 

 

 

• English

The language for the display interface.

 

 

• French*

Language

English

• German*

 

• Spanish*

 

 

 

• Italian*

 

 

 

• Portuguese*

*Language options will vary by model.

 

 

• Japanese*

 

 

 

 

 

 

 

• Good

Select the quality of input utility power.

 

 

• Fair

• If Good is selected, the unit will go on battery power

Local Power

 

• Poor

more often to provide the cleanest power supply to the

Good

 

connected equipment.

Quality

 

• If Poor is selected, the UPS will tolerate more

 

 

 

 

 

fluctuations in power and will go on battery power less

 

 

 

often.

 

 

 

If unsure of the local power quality, select Good.

 

 

 

 

Menu Type

 

Standard or

The Standard menus display a limited set of menus

Standard

and options. The advanced menus include all

Advanced

 

 

parameters.

 

 

 

 

 

 

 

General Settings

Configure these settings at any time. Use the display interface or PowerChute software.

Function

Factory Default

Options

Description

 

 

 

 

 

 

 

 

100

Vac:

108 Vac - 114 Vac

To avoid unnecessary battery usage, set the transfer

 

 

108

Vac

 

 

 

point higher if the utility voltage is chronically high and

 

 

 

 

 

 

 

120

Vac:

 

the connected equipment is known to work under this

High Transfer Point

127 Vac

127 Vac - 136 Vac

condition. The Power Quality setting will

 

 

 

 

automatically change this setting.

 

 

 

 

 

 

 

 

 

 

Note: Use the Advanced Menus to configure this

 

 

230

Vac:

 

 

 

253 Vac - 265 Vac

setting.

 

 

253

Vac

 

 

 

 

 

 

 

 

 

 

8

Smart-UPS 750/1000/1500/2200/3000 VA 100/120/230 Vac / 500 VA 100 Vac Tower

Page 10
Image 10