The MP600M is wired directly from the power source with 20 amps minimum, service utilizing 3 wire grounded cable,
The conduit is connected to the cabinet junction box, or motor starter enclosure on the
OPERATION
To start the air cleaner, close the access door and activate the
Blower Rotation (3 phase power only)
By looking down through the MP600M discharge grille confirm blower rotation agrees with rotation label on motor mount. If rotation is incorrect reverse two (2) input power leads connections in the junction box, switch box or motor starter enclosure. Again verify correct blower rotation.
FILTER CHANGE
Change filter according to the pressure drop across the filter. A minihelic gauge with a range from
Estimated Filter Change Pressure
Main Filter Both Filters | Change | Recommended Final |
| Estimated | Estimated |
95% | 1.8”w.c. | 3.1”w.c. |
HEPA | 1.8”w.c. | 3.1”w.c. |
NOTE:
These readings will vary slightly due to altitude and temperature.
Upon installation of the unit, note the initial pressure reading and record in the table above. Check daily and replace
Once a pattern is established, the
the pressure reading when the
NOTE:
The unit can continue to run beyond the 3.1” w.c. pressure reading; however, airflow will be reduced further.
CAUTION:
To check internal components, disconnect power source to unit to prevent accidental shock.
MAINTENANCE
Precision equipment will require a minimum amount of maintenance to keep it in operating condition. You can perform all normal preventative maintenance. If you are unfamiliar with the terminology used in the in the following sections, refer to the Parts List (Figure
CLEANING AND INSPECTION
Cleaning of Impinger, and inspection and replacement of
CAUTION:
Always disconnect the power source before working on or near any electrical component. If the disconnect point is out of sight, lock it in the proper position and tag to prevent unexpected application of power.
1.Turn unit off.
2.Open access door by turning door latches counter clockwise.
3.Remove filter element,
4.Clean impinger by first rinsing with warm to hot water, then immerse in a commercial grade detergent. Trion recommends our specially formulated Tridex detergent to provide maximum cleaning efficiency on air cleaning equipment. For best results, the cleaning solution should be 140ºF to 160ºF. The impinger should be soaked in the solution for 1½ to 2 hours (longer if extremely dirty).
NOTE:
Using
5.While impinger is soaking, make the following inspections:
10