Some dirt is more tenacious than others to remove and may require a stronger detergent solution. Average settings have been factory set. Best possible settings for any given installation, however, are determined through experience. Determination can be made by visually examining the collecting elements after the first few washings.
To adjust the volume of detergent used within the given time setting, loosen the knurled knob with an Allen wrench on the control valve located in the
4. Routine Maintenance
A.Washing Frequency
The frequency that the collected dirt is to be washed from the unit depends upon the type and amount of dirt in the air to be cleaned. Dirt, which is greasy in nature, tends to harden after collection and should be washed away often. Likewise, units operating under extremely heavy dirt loads should be washed more often as a large
B.Detergent
Effective washing is dependent upon detergent. The detergent reservoir should be examined on a routine basis; a minimum tank level established and never permitted to empty. An empty tank not only means poor washing, but can also be detrimental to the pump. The inside of the tank should be kept clean, free from dirt and foreign objects. The detergent as supplied by Trion, Inc., is formulated specifically for electronic air cleaners and should not be diluted when charging the tank. If substitutes are used, they must be approved by Trion, so as to not void the warranty and should be safe for use in ventilation systems and
C.Electrical Operation
The front panel of the control contains indicating lights for the power supplies, one or two depending on the size of the ATS unit. The lights should be observed on a daily basis to ensure that the electronic air cleaners are operating.
5. Preventative Maintenance
A.Washing frequency – as required.
The washing schedule and detergent reservoir level as outlined under routine maintenance is again referenced here as excessively large contaminant buildup on the collecting elements invites down time. Established routine washing is a preventative maintenance requirement. The frequencies suggested below should be altered if necessary.
B.Fire control system - Every 4 to 6 months or as required.
Inspection, cleaning and servicing of the fire extinguishing system and all listed exhaust hoods shall be completed by properly trained and qualified personnel. For a fire control system supplied with the ATS unit refer to Figure 7.
All actuation components, including remote manual pull stations, mechanical or electrical devices, detectors,
C.Grease removal devices and components – every 4 to 6 months
Hoods, impingers, metal mesh filters, ionizing- collecting cell(s) fan, ducts and other appurtenances shall be cleaned to bare metal at frequent intervals prior to surfaces becoming heavily contaminated with grease or oily sludge. It may be advantageous to clean readily removable items, such as impingers, metal mesh filters,
When a cleaning service is used, a certificate showing date of inspection and/or cleaning should be maintained on the premises. Areas not cleaned will be noted.
Flammable solvents or other flammable cleaning aids shall not be used.
At start of cleaning process, electrical switches that could be accidentally activated shall be locked out. Components of the fire suppression system shall
9